Supply of spare parts for industrial enterprises around the world

Pepperl+Fuchs SJ30-N 106616

Inductive sensor SJ30-N Pepperl+Fuchs 106616
Manufacturer
Pepperl+Fuchs
Name
SJ30-N
Part number
106616
Country
Germany
Type
Inductive sensor
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


Order Pepperl+Fuchs 106616 Spare Parts Online for Enhanced Efficiency

For industries seeking reliable components, Pepperl+Fuchs 106616 Industrial parts are the ideal choice. Built with precision and innovation, these Pepperl+Fuchs 106616 spare parts optimize industrial operations across USA.

What Makes 2technologie Stand Out?

  • Comprehensive Options: A full range of Pepperl+Fuchs 106616 spares for all applications.

  • Swift Delivery: Quick access to Pepperl+Fuchs 106616 spare parts near me or online.

  • Cost-Effective Solutions: Quality Pepperl+Fuchs 106616 Industrial products at the best prices.

  • Proven Expertise: A trusted provider of Pepperl+Fuchs 106616 Industrial components.

Order Pepperl+Fuchs 106616 spare parts today and experience the 2technologie difference!

Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications SJ30-N 106616

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Slot width30 mm
Depth of immersion (lateral)27 ... 30 mm
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 k&Omega,)
Operating voltage5 ... 25 V
Switching frequency0 ... 150 Hz
Hysteresis0.1 ... 0.3 mm
Current consumption
Measuring plate not detected&ge, 3 mA at nominal voltage
Measuring plate detected&le, 1 mA at nominal voltage
Functional safety related parameters
MTTFd5270 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Approvals and certificates
FM approval
Control drawing116-0165
UL approvalcULus Listed, General Purpose
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0453
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated &le,36 V
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection typecable PVC , 2 m
Core cross-section0.75 mm2
Housing materialABS
Degree of protectionIP67
Cable
Bending radius> 10 x cable diameter
Mass450 g
Equipment protection level Ga
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeSJ30-N...
Effective internal capacitancemax. 150 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 1250 µ,H , a cable length of 10 m is considered.
Highest permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1.
Equipment protection level Gb
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeSJ30-N...
Effective internal capacitancemax. 150 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 1250 µ,H , a cable length of 10 m is considered.
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Equipment protection level Da
CE marking[*PD-Z02585A*]
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeSJ30-N...
Effective internal capacitancemax. 150 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 1250 µ,H , a cable length of 10 m is considered.
General information
Use in the hazardous areasee instruction manuals
Category1G, 2G, 1D