General specifications |
Switching function | Normally closed (NC) |
Output type | NAMUR |
Slot width | 3.5 mm |
Depth of immersion (lateral) | 5 ... 7 mm , typ. 6 mm |
Installation | |
Output type | 2-wire |
Nominal ratings |
Nominal voltage | 8.2 V (Ri approx. 1 k&Omega,) |
Operating voltage | 5 ... 25 V |
Switching frequency | 0 ... 3000 Hz |
Hysteresis | 0.8 ... 1.1 mm |
Current consumption | |
| Measuring plate not detected | &ge, 3 mA at nominal voltage |
| Measuring plate detected | &le, 1 mA at nominal voltage |
Functional safety related parameters |
MTTFd | 8760 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives |
Standard conformity | |
| NAMUR | EN 60947-5-6:2000
|
| Standards | EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012 |
Approvals and certificates |
FM approval | |
| Control drawing | 116-0165 |
UL approval | cULus Listed, General Purpose |
CSA approval | cCSAus Listed, General Purpose |
CCC approval | CCC approval / marking not required for products rated &le,36 V |
Ambient conditions |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Mechanical specifications |
Connection type | flexible leads PVC , 500 mm |
Core cross-section | 0.14 mm2 |
Housing material | PBT |
Degree of protection | IP67 |
Equipment protection level Gb |
CE marking | [*PD-Z02585A*] |
ATEX marking | II 2G Ex ia IIC T6&hellip,T1 Gb
The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection Intrinsic safety
Use is restricted to the following stated conditions |
Appropriate type | SJ3,5-H.. |
Effective internal capacitance | max. 50 nF , a cable length of 10 m is considered. |
Effective internal inductance | max. 250 µ,H , a cable length of 10 m is considered. |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. |
Equipment protection level Da |
CE marking | [*PD-Z02585A*] |
ATEX marking | II 1D Ex ia IIIC T135°C Da
The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection Intrinsic safety
Use is restricted to the following stated conditions |
Appropriate type | SJ3,5-H.. |
Effective internal capacitance | max. 50 µ,F
A cable length of 10 m is considered. |
Effective internal inductance | max. 250 µ,H
A cable length of 10 m is considered. |
General information |
Use in the hazardous area | see instruction manuals |
| Category | 2G, 1D |