General specifications |
Switching function | Normally closed (NC) |
Output type | NAMUR |
Rated operating distance | 15 mm |
Installation | flush |
Assured operating distance | 0 ... 12.15 mm |
Reduction factor rAl | 0.4 |
Reduction factor rCu | 0.3 |
Reduction factor r304 | 0.85 |
Output type | 2-wire |
Nominal ratings |
Nominal voltage | 8 V |
Switching frequency | 0 ... 120 Hz |
Current consumption | |
| Measuring plate not detected | min. 3 mA |
| Measuring plate detected | &le, 1 mA |
Functional safety related parameters |
MTTFd | 10750 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives |
Standard conformity | |
| NAMUR | EN 60947-5-6:2000
IEC 60947-5-6:1999 |
| Standards | EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012 |
Approvals and certificates |
FM approval | |
| Control drawing | 116-0165 |
UL approval | |
| Ordinary Location | E87056 |
| Hazardous Location | E501628 |
| Control drawing | 116-0451 |
CSA approval | cCSAus Listed, General Purpose |
CCC approval | CCC approval / marking not required for products rated &le,36 V |
Ambient conditions |
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
Mechanical specifications |
Connection type | screw terminals |
Information for connection | A maximum of two conductors with the same core cross section may be mounted on one terminal connection!
tightening torque 1.2 Nm + 10 % |
Core cross-section | up to 2.5 mm2 |
| Minimum core cross-section | without wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2 |
| Maximum core cross-section | without wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2 |
Housing material | PBT |
Sensing face | PBT |
Degree of protection | IP68 |
Note | Tightening torque: 1.8 Nm (housing) |
Equipment protection level Ga |
CE marking | [*PD-Z02585A*] |
ATEX marking | II 1G Ex ia IIC T6&hellip,T1 Ga
The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012
Ignition protection Intrinsic safety
Use is restricted to the following stated conditions |
Appropriate type | NJ 15+U.+N... |
Effective internal capacitance | max. 140 nF , a cable length of 10 m is considered. |
Effective internal inductance | max. 130 µ,H , a cable length of 10 m is considered. |
Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
Equipment protection level Gb |
CE marking | [*PD-Z02585A*] |
ATEX marking | II 1G Ex ia IIC T6&hellip,T1 Ga
The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection Intrinsic safety
Use is restricted to the following stated conditions |
Appropriate type | NJ 15+U.+N... |
Effective internal capacitance | max. 140 nF , a cable length of 10 m is considered. |
Effective internal inductance | max. 130 µ,H , a cable length of 10 m is considered. |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. |
Equipment protection level Da |
CE marking | [*PD-Z02585A*] |
ATEX marking | II 1D Ex ia IIIC T135°C Da
The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012
Ignition protection Intrinsic safety Use is restricted to the following stated conditions |
Appropriate type | NJ15+U..-N.. |
Effective internal capacitance | max. 140 nF , a cable length of 10 m is considered. |
Effective internal inductance | max. 130 µ,H , a cable length of 10 m is considered. |
General information |
Use in the hazardous area | see instruction manuals |
| Category | 1G, 2G, 1D |