Slots |
Occupied slots | 1 |
Supply |
Connection | backplane bus |
Rated voltage | 12 V DC , only in connection with the power supplies LB9*** |
Power dissipation | 1.5 W |
Power consumption | 2.7 W |
Internal bus |
Connection | backplane bus |
Interface | manufacturer-specific bus to standard com unit |
Analog input |
Number of channels | 4 |
Suitable field devices | |
| Field device | pressure converter |
| Field device [2] | flow converter |
| Field device [3] | level converter |
| Field device [4] | Temperature Converter |
Field device interface | |
| Connection | 2-wire transmitter |
Connection | 2-wire transmitter (HART):
supply circuit: channel I 1+, 2-, channel II 3+, 4-, channel III 5+, 6-, channel IV 7+, 8- |
Transmitter supply voltage | min. 15 V at 20 mA , 21.5 V at 4 mA |
Input resistance | 15 &Omega, |
Conversion time | max. 100 ms |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool |
| Short-circuit | factory setting: > 22 mA configurable between 0 ... 26 mA |
| Open-circuit | factory setting: < 1 mA configurable between 0 ... 26 mA |
HART communication | yes |
HART secondary variable | no |
Transfer characteristics |
Deviation | |
| After calibration | 0.1 % of the signal range at 20 °C (68 °F) |
| Influence of ambient temperature | 0.1 %/10 K of the signal range |
Resolution | 12 Bit (0 ... 26 mA) |
Refresh time | 100 ms |
Indicators/settings |
LED indication | Power LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1-4) red: line fault (lead breakage or short circuit) |
Coding | optional mechanical coding via front socket |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2006 |
Conformity |
Electromagnetic compatibility | NE 21:2007 |
Degree of protection | IEC 60529:2000 |
Environmental test | EN 60068-2-14:2009 |
Shock resistance | EN 60068-2-27:2009 |
Vibration resistance | EN 60068-2-6:2008 |
Damaging gas | EN 60068-2-42:2003 |
Relative humidity | EN 60068-2-78:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 95 % non-condensing |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Vibration resistance | frequency range 10 ... 150 Hz, transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g, 10 cycles
frequency range 5 ... 100 Hz, transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g, 90 minutes at each resonance |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Degree of protection | IP20 when mounted on backplane |
Connection | removable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) |
Mass | approx. 90 g |
Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) |
Data for application in connection with hazardous areas |
Certificate | BVS 12 ATEX E 115 X |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc |
Galvanic isolation | |
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2009
EN 60079-11:2007
EN 60079-15:2010 |
International approvals |
ATEX approval | BVS 12 ATEX E 115 X |
IECEx approval | BVS 11.0068X |
| Approved for | Ex nAc [ic] IIC T4 |
Marine approval | |
| Lloyd Register | 15/20021 |
| Bureau Veritas Marine | 22449/B0 BV |
General information |
System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure. |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |