General specifications |
Signal type | Analog input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | terminals 23, 24 |
Rated voltage | 20 ... 90 V DC or 48 ... 253 V AC |
Power dissipation | 2 W / 3 VA |
Power consumption | 2.2 W / 4 VA |
Interface |
Programming interface | programming socket |
Input |
Connection side | field side |
Connection | terminals 1, 2, 3 |
Input I | |
| Input signal | 0/4 ... 20 mA |
| Available voltage | > 15 V at 20 mA |
| Open circuit voltage/short-circuit current | 24 V / 33 mA |
| Input resistance | 45 &Omega, (terminals 2, 3) |
| Line fault detection | breakage I 22 mA |
Output |
Connection side | control side |
Connection | output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 8+, 7- |
Output signal | 0 ... 20 mA or 4 ... 20 mA |
Output I, II | signal, relay |
| Contact loading | 250 V AC / 2 A / cos &phi, &ge, 0.7 , 40 DC / 2 A |
| Mechanical life | 5 x 107 switching cycles |
Output III | Signal, analog |
| Current range | 0 ... 20 mA or 4 ... 20 mA |
| Open loop voltage | max. 24 V DC |
| Load | max. 650 &Omega, |
| Fault signal | downscale I &le, 3.6 mA, upscale I &ge, 21.5 mA (acc. NAMUR NE43) |
Energized/De-energized delay | 0 ... 250 s , adjustable |
Transfer characteristics |
Input I | |
| Accuracy | < 30 µ,A |
| Influence of ambient temperature | 0.003 %/K (30 ppm) |
Output I, II | |
| Response delay | &le, 200 ms at bounce from 0 ... 20 mA |
Output III | |
| Resolution | &le, 10 µ,A |
| Accuracy | < 20 µ,A |
| Influence of ambient temperature | 0.005 %/K (50 ppm) |
| Reaction time | < 650 ms at bounce from 0 ... 20 mA at the input, 90 % of output full-scale value |
Galvanic isolation |
Input/Other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Mutual output I, II, III | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output III/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Interface/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings |
Display elements | LEDs , display |
Control elements | Control panel |
Configuration | via operating buttons
via PACTware |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Low voltage | |
| Directive 2014/35/EU | EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | 300 g |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-Type Examination Certificate | TÜV 01 ATEX 1701 |
| Marking | II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I |
| Input | Ex ia |
Supply | |
| Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) |
Equipment | terminals 1+, 3- |
| Voltage Uo | 25.8 V |
| Current Io | 93 mA |
| Power Po | 0.603 W |
Equipment | terminals 2-, 3 |
| Voltage Ui | < 30 V |
| Current Ii | 115 mA |
| Voltage Uo | 5 V |
| Current Io | 0.3 mA |
| Power Po | 0.3 mW |
Equipment | terminals 1+, 2 / 3- |
| Voltage Uo | 25.8 V |
| Current Io | 112 mA |
| Power Po | 720 mW |
Output I, II | terminals 10, 11, 12, 16, 17, 18 non-intrinsically safe |
| Maximum safe voltage | 253 V AC / 40 V DC (Attention! Um is no rated voltage.) |
| Contact loading | 253 V AC/2 A/cos &phi, > 0.7, 40 V DC/2 A resistive load (TÜV 01 ATEX 1701)
|
Output III | terminals 8+, 7- non-intrinsically safe |
| Maximum safe voltage Um | 40 V (Attention! The rated voltage can be lower.) |
Interface | RS 232 |
| Maximum safe voltage | 40 V (Attention! The rated voltage can be lower.) , RS 232 |
Galvanic isolation | |
| Input/Other circuits | safe galvanic isolation acc. to EN 50020, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
International approvals |
FM approval | |
| Control drawing | 16-554FM-12 (cFMus) |
IECEx approval | IECEx TUN 09.0007 |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Accessories |
Optional accessories | - FDT framework PACTware 4.1
- device type manager DTM Interface Technology
- adapter K-ADP-USB |