General specifications |
Switching function | Normally closed (NC) |
Output type | NAMUR with safety function |
Rated operating distance | 2 mm |
Installation | flush |
Assured operating distance | 0 ... 1.62 mm |
Reduction factor rAl | 0.4 |
Reduction factor rCu | 0.3 |
Reduction factor r304 | 0.85 |
Safety Integrity Level (SIL) | up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1.
Consider the exida Functional Safety Assessment document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation. |
Output type | 2-wire |
Nominal ratings |
Nominal voltage | 8.2 V |
Switching frequency | 0 ... 3000 Hz |
Suitable for 2:1 technology | yes , with reverse polarity protection diode |
Current consumption | |
| Measuring plate not detected | &ge, 3 mA |
| Measuring plate detected | &le, 1 mA |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 3 |
MTTFd | 10660 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives |
Standard conformity | |
| NAMUR | EN 60947-5-6:2000
IEC 60947-5-6:1999 |
| Standards | EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012 |
Approvals and certificates |
EAC conformity | TR CU 012/2011 |
FM approval | |
| Control drawing | 116-0165 |
UL approval | cULus Listed, General Purpose |
| Ordinary Location | E87056 |
| Hazardous Location | E501628 |
| Control drawing | 116-0454 |
CCC approval | CCC approval / marking not required for products rated &le,36 V |
Ambient conditions |
Ambient temperature | -40 ... 100 °C (-40 ... 212 °F) |
Mechanical specifications |
Connection type | cable silicone , 2 m |
Core cross-section | 0.34 mm2 |
Housing material | stainless steel (303/1.4305) |
Sensing face | Valox (PBT) , black |
Degree of protection | IP68 |
Cable | |
| Bending radius | > 10 x cable diameter |
Data for application in connection with hazardous areas |
Equipment protection level | Ga , Gb , Gc (nA) , Da , Dc , Mb |
Equipment protection level Ga |
Type of protection | intrinsic safety |
CE marking | [*PD-Z02585A*] |
Certificates | |
| Appropriate type | NJ 2-11-SN-G... |
| ATEX certificate | PTB 00 ATEX 2049 X |
| ATEX marking | II 1G Ex ia IIC T6...T1 Ga |
| Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
| IECEx certificate | IECEx PTB 11.0092X |
| IECEx marking | Ex ia IIC T6...T1 Ga |
| Standards | IEC 60079-0:2011 , IEC 60079-11:2011 |
Effective internal capacitance | max. 50 µ,F
A cable length of 10 m is considered. |
Effective internal inductance | max. 150 µ,H
A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values. |
| for ATEX | at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 59 °C (138.2 °F)
T5 : 71 °C (159.8 °F)
T4 : 99 °C (210.2 °F)
T3 : 99 °C (210.2 °F)
T2 : 99 °C (210.2 °F)
T1 : 99 °C (210.2 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 56 °C (132.8 °F)
T5 : 68 °C (154.4 °F)
T4 : 96 °C (204.8 °F)
T3 : 96 °C (204.8 °F)
T2 : 96 °C (204.8 °F)
T1 : 96 °C (204.8 °F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 45 °C (113 °F)
T5 : 57 °C (134.6 °F)
T4 : 81 °C (177.8 °F)
T3 : 81 °C (177.8 °F)
T2 : 81 °C (177.8 °F)
T1 : 81 °C (177.8 °F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 37 °C (98.6 °F)
T5 : 49 °C (120.2 °F)
T4 : 63 °C (145.4 °F)
T3 : 63 °C (145.4 °F)
T2 : 63 °C (145.4 °F)
T1 : 63 °C (145.4 °F) |
| for IECEx | at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 76 °C (168.8 °F)
T5 : 91 °C (195.8 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 73 °C (163.4 °F)
T5 : 88 °C (190.4 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 62 °C (143.6 °F)
T5 : 77 °C (170.6 °F)
T4 : 81 °C (177.8 °F)
T3 : 81 °C (177.8 °F)
T2 : 81 °C (177.8 °F)
T1 : 81 °C (177.8 °F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 54 °C (129.2 °F)
T5 : 63 °C (145.4 °F)
T4 : 63 °C (145.4 °F)
T3 : 63 °C (145.4 °F)
T2 : 63 °C (145.4 °F)
T1 : 63 °C (145.4 °F) |
Equipment protection level Gb |
Type of protection | intrinsic safety |
CE marking | [*PD-Z02585A*] |
Certificates | |
| Appropriate type | NJ 2-11-SN-G... |
| ATEX certificate | PTB 00 ATEX 2049 X |
| ATEX marking | II 1G Ex ia IIC T6&hellip,T1 Ga |
| Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
| IECEx certificate | IECEx PTB 11.0092X |
| IECEx marking | Ex ia IIC T6...T1 Ga |
| Standards | IEC 60079-0:2011 , IEC 60079-11:2011 |
Effective internal capacitance | max. 50 nF
A cable length of 10 m is considered. |
Effective internal inductance | max. 150 µ,H
A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 76 °C (168.8 °F)
T5 : 91 °C (195.8 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 73 °C (163.4 °F)
T5 : 88 °C (190.4 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 62 °C (143.6 °F)
T5 : 77 °C (170.6 °F)
T4 : 81 °C (177.8 °F)
T3 : 81 °C (177.8 °F)
T2 : 81 °C (177.8 °F)
T1 : 81 °C (177.8 °F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 54 °C (129.2 °F)
T5 : 63 °C (145.4 °F)
T4 : 63 °C (145.4 °F)
T3 : 63 °C (145.4 °F)
T2 : 63 °C (145.4 °F)
T1 : 63 °C (145.4 °F) |
Equipment protection level Gc (nA) |
Type of protection | n |
CE marking | [*PD-Z02586A*] |
Certificates | |
| ATEX certificate | PF 15 CERT 3754 X |
| ATEX marking | II 3G Ex nA IIC T6 Gc |
| Standards | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
Possible characteristics | maximum operating voltage UBmax , maximum load current ILmax , minimum series resistance RV , maximum analog output voltage UAmax , maximum analog output current IAmax |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
using an amplifier in accordance with EN 60947-5-6 : 61 °C (141.8 °F)
at UBmax = 9 V , RV = 562 &Omega, : 61 °C (141.8 °F) |
Equipment protection level Da |
Type of protection | intrinsic safety |
CE marking | [*PD-Z02585A*] |
Certificates | |
| Appropriate type | NJ 2-11-SN-G... |
| ATEX certificate | PTB 00 ATEX 2049 X |
| ATEX marking | II 1D Ex ia IIIC T135°C Da |
| Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
| IECEx certificate | IECEx PTB 11.0092X |
| IECEx marking | Ex ia IIIC T135°C Da |
| Standards | IEC 60079-0:2011 , IEC 60079-11:2011 |
Effective internal capacitance | max. 50 nF
A cable length of 10 m is considered. |
Effective internal inductance | max. 150 µ,H
A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 81 °C (177.8 °F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 63 °C (145.4 °F) |
Equipment protection level Dc |
Type of protection | Protection by enclosure tc |
CE marking | [*PD-Z02586A*] |
Certificates | |
| ATEX certificate | PF 15 CERT 3774 X |
| ATEX marking | II 3D Ex tc IIIC T80 °C Dc |
| Standards | EN 60079-0:2012+A11:2013 , EN 60079-31:2014 |
Possible characteristics | maximum operating voltage UBmax , maximum load current ILmax , minimum series resistance RV , maximum analog output voltage UAmax , maximum analog output current IAmax |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
using an amplifier in accordance with EN 60947-5-6 : 61 °C (141.8 °F)
at UBmax = 9 V , RV = 562 &Omega, : 61 °C (141.8 °F) |
Equipment protection level Mb |
Type of protection | intrinsic safety |
Certificates | |
| Appropriate type | NJ 2-11-SN-G... |
| IECEx certificate | IECEx PTB 11.0092X |
| IECEx marking | Ex ia I Mb |
| Standards | IEC 60079-0:2011 , IEC 60079-11:2011 |
Effective internal capacitance | max. 50 nF
A cable length of 10 m is considered. |
Effective internal inductance | max. 150 µ,H
A cable length of 10 m is considered.
|
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 81 °C (177.8 °F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 63 °C (145.4 °F) |
General information |