General specifications |
Signal type | Digital Input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | SL1: 1a(-), 1b(-), 2a(+), 2b(+) |
Rated voltage | 19 ... 30 V DC bus powered via Termination Board |
Ripple | &le, 10 % |
Rated current | &le, 25 mA |
Power dissipation | &le, 500 mW |
Power consumption | &le, 600 mW |
Input |
Connection side | field side |
Connection | SL2: 5a(+), 5b(-) |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection | breakage I &le, 0.1 mA , short-circuit I &ge, 6.5 mA |
Pulse/Pause ratio | min. 100 µ,s / min. 100 µ,s |
Output |
Connection side | control side |
Connection | SL1: 8a(+), 7a(-), 10a(+), 9a(-) |
Rated voltage | 19 ... 30 V DC with external resistance > 2 k&Omega,, e. g. 16-channel ProSafe DI card SDV144 from Yokogawa |
Response time | &le, 200 µ,s |
Output I, II | signal or error message, passive transistor output (resistive)
0-signal: 33 k&Omega, ± 5 % + voltage drop 6.5 V ± 0.5 V
1-signal: voltage drop 6.5 V ± 0.5 V
fault: > 100 k&Omega, |
Fault indication output |
Connection | SL1: 6b |
Output type | open collector transistor (internal fault bus) |
Transfer characteristics |
Switching frequency | &le, 5 kHz |
Galvanic isolation |
Output/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff |
Output/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP-switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 |
Degree of protection | IEC 60529:2001 |
Protection against electrical shock | IEC 61010-1 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Mass | approx. 100 g |
Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
Mounting | on Termination Board |
Coding | pin 1 and 2 trimmed
For further information see system description. |
Data for application in connection with hazardous areas |
EU-Type Examination Certificate | BVS 11 ATEX E 026 |
| Marking | II (1) G [Ex ia] IIC
II (1) D [Ex ia] IIIC
I (M1) [Ex ia] I |
| Input | Ex ia |
| Voltage | 10.5 V |
| Current | 17.1 mA |
| Power | 45 mW (linear characteristic) |
Supply | |
| Maximum safe voltage | 253 V AC (Attention! Um is no rated voltage.) |
Output | |
| Maximum safe voltage | 253 V AC (Attention! Um is no rated voltage.) |
Certificate | KIWA 15 ATEX 0037 X |
| Marking | II 3G Ex ec IIC T4 Gc |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018 , EN 50303:2000 |
International approvals |
FM approval | |
| Control drawing | 116-0430 (cFMus) |
UL approval | |
| Control drawing | 116-0331 |
IECEx approval | |
| IECEx certificate | IECEx BVS 11.0040
IECEx KIWA 15.0019X |
| IECEx marking | [Ex ia Ga] IIC, [Ex ia] IIIC , [Ex ia] I
Ex ec IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |