Supply of spare parts for industrial enterprises around the world
Home Brands Pepperl+Fuchs 241590 KFD0-CS-EX1.54-Y2

Pepperl+Fuchs KFD0-CS-EX1.54-Y2 241590

Repeater KFD0-CS-EX1.54-Y2 Pepperl+Fuchs 241590
Manufacturer
Pepperl+Fuchs
Name
KFD0-CS-EX1.54-Y2
Part number
241590
Country
Germany
Type
Repeater
Weight (g)
117
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


This isolated barrier is used for intrinsic safety applications. It provides control and signal transfer for SMART compatible fire and smoke alarm transmitters inside hazardous areas. The typical application for the barrier is connection of a fire detector loop to a control panel through a System Sensor® translator device (typically an IST200). The fall time of the digital signal must be less than 50 s, the current in the hazardous area must be bigger than 1 mA. Since this isolator is loop-powered, use the technical data to verify that proper voltage is available to the field devices.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications KFD0-CS-EX1.54-Y2 241590

General specifications
Signal typeAnalog input
Supply
Rated voltageloop powered
Power dissipation0.2 W
Control circuit
Connectionterminals 11+, 12-
Current0 ... 20 mA
Transmission rangecurrent: 1 ... 20 mA voltage: 0 ... 24 V
Field circuit
Connectionterminals 1+, 2-
Short-circuit current&le, 65 mA
Transfer characteristics
Deviation
After calibration&le, 3.5 mA current loss at 20 mA load current
Influence of ambient temperature± 20 µ,A / K
Rise time/fall time&le, 50 µ,s (load current &ge, 1 mA)
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Indicators/settings
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateBAS 00 ATEX 7087
Marking II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I (-20 °C &le, Tamb &le, 60 °C)
Voltage25.2 V
Current43 mA
Power271 mW
Supply
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
CertificateTÜV 99 ATEX 1499 X
Marking II 3G Ex nA II T4 [device in zone 2]
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0129 (cFMus)
UL approval
Control drawing116-0348 (cULus)
IECEx approvalIECEx BAS 08.0079 IECEx BAS 10.0007X
Approved for[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.