General specifications |
Signal type | Digital Output |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 3 |
Supply |
Rated voltage | loop powered |
Power dissipation | < 1.05 W (&le, 30 V) per channel |
Input |
Connection side | control side |
Connection | terminals 7, 8, 8, 9 |
Rated voltage | 20 ... 35 V DC |
Current | 72 mA at 20 V input voltage, load = 220 &Omega,
50 mA at 35 V input voltage, load = 220 &Omega, |
Inrush current | &le, 200 mA after 100 µ,s |
Output |
Connection side | field side |
Connection | terminals 1+, 2-, 4+, 5- |
Internal resistor | max. 282 &Omega, |
Current | &le, 45 mA |
Voltage | &ge, 10 V |
Open loop voltage | min. 22.7 V |
Output rated operating current | 45 mA |
Output signal | These values are valid for the rated operating voltage 20 ... 35 V DC. |
Energized/De-energized delay | single operation: typ. 1.7 ms/50 µ,s, periodical: typ. 5 µ,s/50 µ,s |
Indicators/settings |
Display elements | LEDs |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Protection against electrical shock | UL 61010-1:2004 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | BASEEFA 06 ATEX 0252 |
| Marking | II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I (-20 °C &le, Tamb &le, 60 °C)
|
| Voltage | 25.2 V |
| Current | 93 mA |
| Power | 590 mW |
Input | |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Certificate | TÜV 99 ATEX 1499 X |
| Marking | II 3G Ex nA II T4 [device in zone 2] |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
FM approval | |
| Control drawing | 116-0309 |
UL approval | |
| Control drawing | 116-0316 (cULus) |
IECEx approval | |
| IECEx certificate | IECEx BAS 06.0058
IECEx CML 19.0093X |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |