Supply of spare parts for industrial enterprises around the world
Home Brands Pepperl+Fuchs 242031 KFD0-SD2-EX1.1045

Pepperl+Fuchs KFD0-SD2-EX1.1045 242031

Solenoid Driver KFD0-SD2-EX1.1045 Pepperl+Fuchs 242031
Manufacturer
Pepperl+Fuchs
Name
KFD0-SD2-EX1.1045
Part number
242031
Country
Germany
Type
Solenoid Driver
Weight (g)
123
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


This isolated barrier is used for intrinsic safety applications. The device supplies power to solenoids, LEDs and audible alarms located in a hazardous area. The device is loop powered, so the available energy at the output is received from the input signal. The output signal has a resistive characteristic. As a result the output voltage and current are dependent on the load and the input voltage At full load, 10 V at 45 mA is available for the hazardous area application.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications KFD0-SD2-EX1.1045 242031

Product Description
current limit 45 mA
General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
Rated voltageloop powered
Power dissipation< 1.05 W (&le, 30 V)
Input
Connection sidecontrol side
Connectionterminals 7, 8
Rated voltage20 ... 35 V DC
Current72 mA at 20 V input voltage, load = 220 &Omega, 50 mA at 35 V input voltage, load = 220 &Omega,
Inrush current&le, 200 mA after 100 µ,s
Output
Connection sidefield side
Connectionterminals 1+, 2-
Internal resistormax. 282 &Omega,
Current&le, 45 mA
Voltage&ge, 10 V
Open loop voltagemin. 22.7 V
Output rated operating current45 mA
Output signalThese values are valid for the rated operating voltage 20 ... 35 V DC.
Energized/De-energized delaysingle operation: typ. 1.7 ms/50 µ,s, periodical: typ. 5 µ,s/50 µ,s
Indicators/settings
Display elementsLED
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2004
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 06 ATEX 0252
Marking II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I (-20 °C &le, Tamb &le, 60 °C)
Voltage25.2 V
Current93 mA
Power590 mW
Input
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
CertificateTÜV 99 ATEX 1499 X
Marking II 3G Ex nA II T4 [device in zone 2]
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0309
UL approval
Control drawing116-0316 (cULus)
IECEx approval
IECEx certificateIECEx BAS 06.0058 IECEx CML 19.0093X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.