Supply of spare parts for industrial enterprises around the world
Home Brands Pepperl+Fuchs 224579 KFD0-RSH-1.4S.PS2

Pepperl+Fuchs KFD0-RSH-1.4S.PS2 224579

Relay module KFD0-RSH-1.4S.PS2 Pepperl+Fuchs 224579
Manufacturer
Pepperl+Fuchs
Name
KFD0-RSH-1.4S.PS2
Part number
224579
Country
Germany
Type
Relay module
Weight (g)
165
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


This signal conditioner is a relay module that is suitable for safely switching applications of a load circuit. The device isolates load circuits up to 230 V and the 24 V control interface. The energized to safe (ETS) function is permitted for SIL3 applications with output I. The de-energized to safe (DTS) function is permitted for SIL3 applications with output II. Additionally a dual pole switching (DPS) is possible by combination of output I and II. The relays are of diverse design, but have a common effect on the individual switch output. For checking of these relays, terminals 10, 11 and 12 can be used. The test mode will be indicated by LEDs according to NAMUR NE44. The outputs are galvanically isolated from the input. Output II is protected against contact welding by a fuse depending on the used terminal.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications KFD0-RSH-1.4S.PS2 224579

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
Rated voltageloop powered
Power dissipation< 1.5 W
Power consumption< 1.5 W
Input
Connection sidecontrol side
ConnectionInput terminals 7, 8 , test input terminals 10, 11, 12
Pulse/Pause ratiomin. 20 ms / min. 20 ms
Test inputsee Functional Safety Manual
Signal level0-signal: -3 ... 3 V DC 1-signal: 20 ... 26.5 V
Rated current45 ... 50 mA
Output
Connection sidefield side
Connectionoutput I (ETS): terminals 2, 3 output II (DTS): terminals 4, 5, 6 output I and II (DPS): terminals 2, 3, 4, 5, 6
Contact loading253 V AC/5 A/cos &phi, 0.7, 30 V DC/5 A resistive load
Minimum switch current2 mA / 24 V DC
Energized/De-energized delayapprox. 10 ms / approx. 5 ms
Mechanical life5 x 106 switching cycles
Fuse rating2.5 A (max. 5 A) recommended maximum utilization of the fuse: 80 %
Transfer characteristics
Switching frequency< 10 Hz
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2012
Degree of protectionIEC 60529:2013
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
CertificatePF 15 CERT 3844 X
Marking II 3G Ex nA nC IIC T4 Gc [device in zone 2]
Output
Contact loading50 V AC/4 A, 30 V DC/4 A , see derating curves for Zone 2
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013, EN 60079-15:2010
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.