General specifications |
Switching function | Normally closed (NC) |
Output type | NAMUR |
Rated operating distance | 8 mm |
Installation | non-flush |
Assured operating distance | 0 ... 6.48 mm |
Actual operating distance | 7.2 ... 8.8 mm typ. 8 mm |
Reduction factor rAl | 0.42 |
Reduction factor rCu | 0.4 |
Reduction factor r304 | 0.72 |
Output type | 2-wire |
Nominal ratings |
Nominal voltage | 8 V |
Switching frequency | 0 ... 300 Hz |
Hysteresis | 1 ... 15 typ. 5 % |
Reverse polarity protection | reverse polarity protected |
Short-circuit protection | yes |
Current consumption | |
| Measuring plate not detected | min. 3 mA |
| Measuring plate detected | &le, 1 mA |
Switching state indicator | all direction LED, yellow |
Functional safety related parameters |
MTTFd | 2040 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives |
Standard conformity | |
| NAMUR | EN 60947-5-6:2000
IEC 60947-5-6:1999 |
| Standards | EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012 |
Approvals and certificates |
EAC conformity | TR CU 012/2011 |
FM approval | |
| Control drawing | 116-0165 |
UL approval | |
| Ordinary Location | E87056 |
| Hazardous Location | E501628 |
| Control drawing | 116-0452 |
CSA approval | cCSAus Listed, General Purpose |
CCC approval | CCC approval / marking not required for products rated &le,36 V |
Ambient conditions |
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
Mechanical specifications |
Connection type | cable PVC , 10 m |
Core cross-section | 0.75 mm2 |
Housing material | Stainless steel 1.4305 / AISI 303 |
Sensing face | PBT |
Degree of protection | IP67 |
Cable | |
| Cable diameter | 6 mm ± 0.2 mm |
| Bending radius | > 10 x cable diameter |
Equipment protection level Ga |
CE marking | [*PD-Z02585A*] |
ATEX marking | II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety
Use is restricted to the following stated conditions |
Appropriate type | NCN8-18GM...-N0... |
Effective internal capacitance | max. 95 nF , a cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H , a cable length of 10 m is considered. |
Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
Equipment protection level Gb |
CE marking | [*PD-Z02585A*] |
ATEX marking | II 1G Ex ia IIC T6&hellip,T1 Ga
The Ex-significant identification is on the enclosed adhesive label |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety
Use is restricted to the following stated conditions |
Appropriate type | NCN8-18GM...-N0... |
Effective internal capacitance | max. 95 nF , a cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H , a cable length of 10 m is considered. |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. |
Equipment protection level Gc (ic) |
Certificate | PF 13 CERT 2895 X |
CE marking | [*PD-Z02586A*] |
ATEX marking | II 3G Ex ic IIC T6&hellip,T1 Gc
The Ex-significant identification is on the enclosed adhesive label |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection category ic Use is restricted to the following stated conditions |
Effective internal capacitance | max. 95 nF , a cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H , A cable length of 10 m is considered.
|
Special conditions | |
| for Pi=34 mW, Ii=25 mA, T6 | 55 °C (131 °F) |
| for Pi=34 mW, Ii=25 mA, T5 | 55 °C (131 °F) |
| for Pi=34 mW, Ii=25 mA, T4-T1 | 55 °C (131 °F) |
| for Pi=64 mW, Ii=25 mA, T6 | 55 °C (131 °F) |
| for Pi=64 mW, Ii=25 mA, T5 | 55 °C (131 °F) |
| for Pi=64 mW, Ii=25 mA, T4-T1 | 55 °C (131 °F) |
| for Pi=169 mW, Ii=52 mA, T6 | 52 °C (125.6 °F) |
| for Pi=169 mW, Ii=52 mA, T5 | 52 °C (125.6 °F) |
| for Pi=169 mW, Ii=52 mA, T4-T1 | 52 °C (125.6 °F) |
| for Pi=242 mW, Ii=76 mA, T6 | 44 °C (111.2 °F) |
| for Pi=242 mW, Ii=76 mA, T5 | 44 °C (111.2 °F) |
| for Pi=242 mW, Ii=76 mA, T4-T1 | 44 °C (111.2 °F) |
Equipment protection level Da |
CE marking | [*PD-Z02585A*] |
ATEX marking | II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety
Use is restricted to the following stated conditions |
Appropriate type | NCN8-18GM...-N0... |
Effective internal capacitance | max. 95 nF , a cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H , a cable length of 10 m is considered. |
Maximum permissible ambient temperature |
Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. |
General information |
Use in the hazardous area | see instruction manuals |
| Category | 1G, 2G, 1D |