General specifications |
Signal type | Analog input |
Supply |
Connection | Power Rail or terminals 14+, 15- |
Rated voltage | 19 ... 30 V DC |
Ripple | within the supply tolerance |
Rated current | &le, 11 mA |
Power dissipation/power consumption | 0.3 W max. |
Input |
Connection side | field side |
Connection | terminals 4+, 5- |
Input resistance | min. 20 M&Omega, |
Transmission range | -50 ... 50 mV |
Offset voltage/current | &le, 5 µ,V / &le, 5 nA |
Line fault detection | 100 nA |
Output |
Connection side | control side |
Connection | terminals 7+, 8- |
Load | Accuracy figures for infinite load impedance. Additional 0.03 % of span for a load resistance of 10 k&Omega, |
Voltage | -50 ... 50 mV |
Fault signal | sensor breakage: > +100 mV (upscale), < -100 mV (downscale) |
Output resistance | max. 3 &Omega, |
Transfer characteristics |
Cut-off frequency | 350 Hz (-3 dB) |
Deviation | |
| After calibration | at 20 °C (68 °F): ± 3 µ,V up to ± 10 mV/± 0.03 % of the span up to +50 mV/± 0.05 % of the span up to -50 mV |
| Influence of ambient temperature | ± 1 µ,V/K (typical ± 0.25 µ,V/K) |
Absolute | < 0.25 K at 30 V voltage supply |
Rise time | &le, 1 ms |
Galvanic isolation |
Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Indicators/settings |
Display elements | LED |
Control elements | DIP-switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21 |
Degree of protection | IEC 60529 |
Protection against electrical shock | UL 61010-1 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 125 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-Type Examination Certificate | BASEEFA 06 ATEX 0040 |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le, Tamb &le, 60 °C) , [circuit(s) in zone 0/1/2] |
| Voltage | 5.5 V DC |
| Current | 2.4 mA |
| Power | 3.3 mW |
Supply | |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Certificate | BASEEFA 09 ATEX 0219X |
| Marking | II 3G Ex ec IIC T4 Gc |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 |
International approvals |
UL approval | |
| Control drawing | 116-0334 (cULus) |
IECEx approval | |
| IECEx certificate | IECEx BAS 06.0011
IECEx BAS 09.0103X |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Accessories |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03) |