General specifications |
Signal type | Digital Input |
Supply |
Connection | terminals 17, 18 |
Rated voltage | 198 ... 253 V AC , 45 ... 65 Hz |
Power dissipation | 2.5 W |
Power consumption | approx. 3.2 VA |
Input |
Connection side | field side |
Connection | terminals 1-, 2+, 8+, 9- |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Pulse/Pause ratio | min. 0.5 ms / min. 0.5 ms |
Line fault detection | breakage I &le, 0.1 mA |
Output |
Connection side | control side |
Connection | terminals 10, 11, 12, 13, 14, 15 |
Output | signal , relay |
Contact loading | 253 V AC/2 A/500 VA/cos &phi, min. 0,7, 125 V AC/4 A/500 VA cos &phi, min. 0,7, 40 V DC/2 A/80 W ohmic load |
Energized/De-energized delay | approx. 10 ms / approx. 20 ms |
Mechanical life | 107 switching cycles |
Transfer characteristics |
Switching frequency | < 10 Hz |
Galvanic isolation |
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings |
Display elements | LEDs |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Low voltage | |
| Directive 2014/35/EU | EN 61010-1:2010 |
Conformity |
Degree of protection | IEC 60529 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 410 g |
Dimensions | 60 x 104 x 110 mm (2.4 x 4.1 x 4.3 inch) |
Data for application in connection with hazardous areas |
EU-Type Examination Certificate | PTB 02 ATEX 2065 |
| Marking | II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2] |
| Input | Ex ia |
| Voltage | 13.4 V DC |
| Current | 31 mA |
| Power | 145 mW (trapezoid characteristic curve) |
Supply | |
| Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) |
Output | |
| Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |