Supply of spare parts for industrial enterprises around the world
Home Brands Pepperl+Fuchs 129377 VAN-115/230AC-K16 ASI-Ne

Pepperl+Fuchs VAN-115/230AC-K16 ASI-Ne 129377

Power supply VAN-115/230AC-K16 ASI-Ne Pepperl+Fuchs 129377
Manufacturer
Pepperl+Fuchs
Name
VAN-115/230AC-K16 ASI-Ne
Part number
129377
Country
Germany
Type
Power supply
Weight (g)
1013
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


The primary pulsed DIN rail power pack is used for special power supply of AS-Interface networks via a two-wire line. It supplies a fully loaded AS-Interface system with an output current of 8 A. The voltage input range of the device can be selected on the front side. This makes it possible to operate the device on all single-phase power supply voltages commonly used worldwide. Certification of the device according to international and various national standards allows for worldwide usage. Safe operation using FUSE mode: To protect against overload and excess temperature, the device has a FUSE mode (electronically simulated fuse), for permanent shutoff of the output in the event of failure. This turns off the device in the event of overload, short circuit or excess temperature, thus protecting the AS-Interface cable and the attached components. A flashing LED indicates that the FUSE mode has been triggered. Turning the device on again requires deliberately pressing a Reset button on the front side of the unit. This prevents unwanted startup from occurring. Operation without the AS-Interface string: This AS-Interface power pack has an inductive output. For operation without the AS-Interface string (for example lab measurements) we recommend connecting a 470 μF/35 V capacitor between AS-Interface + and AS-Interface -. Standard commercial laboratory loads frequently tend to oscillate and together with the data decoupling form a resonance that exceeds the permitted modulation voltage.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications VAN-115/230AC-K16 ASI-Ne 129377

Product Description
AS-Interface power supply, data decoupling, 8 A
General specifications
UL File NumberE223176
MTBF100 a
Indicators/operating means
Reset push-button switchFUSE mode reset
Power selection switchchangeover switch for 115 V AC/230 V AC
LED Overloadred LED, flashes in the FUSE mode
LED IR onred LED: ON: Plug-in jumper position 2-3 OFF: Plug-in jumper position 1-2
Plug-in jumperPosition 1-2: Communication Mode Position 2-3: IR addressing
LED AS-i okoperating display, LED green
Electrical specifications
FusingT8A/250 V AC HBC (not accessible)
Capacity factor> 0.5
Rated operating voltagenominal: 100 ... 120 V AC/220 ... 240 V AC (front end selectable) permissible: 85 ... 132 V AC/184 ... 264 V AC/230 ... 375 V DC
Rated operating current6,0 A (Switch position 115 V) 2.8 A (Switch position 230 V)
Supply frequency47 ... 63 Hz or DC
Efficiencytyp. 92 % (at 230 V AC/8 A)
Surge protectionlimited to max. 55 V
Output
Short-circuit protection/overloadFUSE Mode (2 ... 5 s current, then trips)
Current limit> 8.4 A
Voltage30.55 V DC ± 3 %
Current8 A
Galvanic isolationovervoltage category III
Residual ripple&le, 50 mVss (500 kHz bandwidth, 50-&Omega,-measurement with ohmic load)
Short-circuit current12 ... 25 A (max. 5 s)
Standard conformity
Electromagnetic compatibilityemitted interference in accordance with EN 50081-2 class B (EN 55011, EN 55022) noise immunity in accordance with EN 61000-6-2, EN 61000-4-2 to EN 61000-4-6, EN 61000-4-11
Ambient conditions
Ambient temperature-10 ... 70 °C (14 ... 158 °F) (Measured 25 mm below the device) from 60° C 6W/°C power recovery necessary
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Pollution degree2
Mechanical specifications
Degree of protectionIP20 according to EN 60529
Protection class1 (IEC 60536), Protective conductor connection necessary
ConnectionConnection terminals, max. conductor cross-section flexible: 0.5 ... 4 mm2 fixed: 0.5 ... 6 mm2 stripped length 7 mm, connector sleeves are permissible
Material
Housingmetal
Massapprox. 890 g