Pepperl+Fuchs HiD2072 121445

Signal Converter HiD2072 Pepperl+Fuchs 121445
Manufacturer
Pepperl+Fuchs
Name
HiD2072
Part number
121445
Country
Germany
Type
Signal Converter
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


This isolated barrier is used for intrinsic safety applications. It is a temperature converter that accepts inputs from resistance temperature detectors (RTD) or potentiometers from a hazardous area and converts them to an isolated analog current signal in the safe area. Input type, range, and error handling parameters are configurable by DIP switches and potentiometers. The outputs are isolated from the inputs and are referenced to the power supply common. This module mounts on a HiD Termination Board.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications HiD2072 121445

General specifications
Signal typeAnalog input
Supply
ConnectionSL1: 1a(-), 1b(-), 2a(+), 2b(+)
Rated voltage20.4 ... 30 V DC bus powered via Termination Board
Rated current30 mA at 24 V, 20 mA output (per channel)
Power dissipation0.6 W at 24 V (per channel)
Input
Connection sidefield side
ConnectionSL2: 7a(+), 5a(-), 5b(+), 7b(-), 3a(+), 1a(-), 1b(+), 3b(-)
RTD2-, 3- or 4-wire Pt100 acc. to DIN 43760
Measuring currentmax. 0.4 mA
Measurement range-200 ... 850 °C (-328 ... 1562 °F)
Span limits40 ... 850 °C (104 ... 1562 °F)
Zero suppression± 500 % of span
Potentiometer3-wire
Measurement range100 ... 300 &Omega, or 0.3 ... 100 k&Omega, with external shunt
Line fault detectionsensor burnout, upscale or downscale (selectable) (not on potentiometer and 4-wire RTD)
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-), 10a(+), 9a(-)
Load0 ... 650 &Omega,
Output signal4 ... 20 mA or 1 ... 5 V (on 250 &Omega,, 0.1 % internal shunt) Output signal is linear with temperature for Pt100.
Ripple10 mVrms (at load 250 &Omega,)
Transfer characteristics
Accuracy< ± 0.1 % of full-scale value (current output)
Influence of temperature< ± 0.01 %/K on zero and span
Influence of load< ± 0.1 % of full-scale value from 0 ... 650 &Omega,
Rise time/fall timetyp. 150 ms
Linearity< ± 0.1 % of full-scale value (terminal based °C or °F input to mA out for Pt100)
Indicators/settings
Display elementsLED
Control elementsDIP-switch potentiometer
Configurationvia DIP switches via potentiometer
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006 For further information see system description.
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 140 g
Dimensions18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Mountingon Termination Board
Data for application in connection with hazardous areas
EU-Type Examination CertificateCESI 02 ATEX 086
Marking II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC
CertificatePF 11 CERT 2109 X
Marking II 3G Ex nA IIC T4 Gc [device in zone 2]
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
CSA approval
Control drawing366-005CS-12B (cCSAus)
IECEx approvalIECEx TUN 04.0012
Approved for[Ex ia] IIC