General specifications |
Signal type | Analog input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | SL1: 1a(-), 1b(-), 2a(+), 2b(+) |
Rated voltage | 20.4 ... 30 V DC bus powered via Termination Board |
Rated current | 40 mA at 24 V, 20 mA output (per channel) |
Power dissipation | 1.05 W at 20 mA and 24 V external from PCS or PLC (per channel) |
Input |
Connection side | field side |
Connection | SL2: 5a(+), 5b, 7a(-), 1a(+), 1b, 3b(-) |
Input current | 4 ... 20 mA , current limit 26 mA |
Input resistance | 40 &Omega, , for current source |
Ripple | 10 mV eff |
Voltage | min. 15.5 V at 20 mA |
Communication | pass-through of HART signal to safe area
The current sink terminals 4, 7 and 5, 6 do not pass the HART signal to safe area. |
Output |
Connection side | control side |
Connection | SL1: 8a(+), 7a(-), 10a(+), 9a(-) |
Output | sink mode from external supply |
Output signal | 4 ... 20 mA , current limit 24 mA |
Voltage | working voltage 7 ... 30 V |
Response time | 70 ms , 10 ... 90 % step change |
Signal level | no fault: 1 mA ... 23.5 mA input current
fault detection: 24 mA input current |
Fault indication output |
Connection | SL1: 6b |
Output type | open collector transistor (common to both channels)
fault bus signal, collective error message |
Transfer characteristics |
Calibrated accuracy | < ± 0.1 % of full-scale value |
Influence of temperature | < ± 0.01 %/ K |
Frequency range | communication channel: 0.5 ... 40 kHz within 3 db, (-6 db at 100 kHz), Tx to output and output to Tx,
suitable for use with SMART transmitters using HART or similar protocol |
Linearity | < ± 0.05 % of full-scale value |
Galvanic isolation |
Output/power supply | functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff |
Output/Output | functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff |
Indicators/settings |
Display elements | LEDs |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2006
For further information see system description. |
Degree of protection | IEC 60529 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Relative humidity | 5 ... 90 %, non-condensing up to 35 °C (95 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Mass | approx. 140 g |
Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
Mounting | on Termination Board |
Coding | pin 1 and 3 trimmed
For further information see system description. |
Data for application in connection with hazardous areas |
EU-type examination certificate | CESI 02 ATEX 086 |
| Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC |
| Input | Ex ia, Ex iaD |
| Voltage | 26 V |
| Current | 93 mA |
| Power | 605 mW |
Supply | |
| Maximum safe voltage | 250 V AC (Attention! Um is no rated voltage.) |
Certificate | PF 11 CERT 2109 X |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] |
Galvanic isolation | |
| Input/input | safe electrical isolation acc. to EN 60079-11:2007, voltage peak value 60 V |
| Input/Output | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
CSA approval | |
| Control drawing | 366-005CS-12B (cCSAus) |
IECEx approval | IECEx TUN 04.0012 |
| Approved for | [Ex ia] IIC |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |