Supply of spare parts for industrial enterprises around the world

Pepperl+Fuchs HiD2030 121495

Transmitter Power Supply HiD2030 Pepperl+Fuchs 121495
Manufacturer
Pepperl+Fuchs
Name
HiD2030
Part number
121495
Country
Germany
Type
Transmitter Power Supply
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


This isolated barrier is used for intrinsic safety applications. It provides a fully floating supply to power 2-wire SMART transmitters in the hazardous area, and repeats the current to drive a safe area load. It is also used with 2-wire current sources. Digital signals may be superimposed on the analog values in the hazardous or safe area, which are transferred bidirectionally. A separate fault output on the bus is signaled if the input signal is outside the range 0.2 mA ... 24 mA. The fault conditions can be monitored via a Fault Indication Board. This module mounts on a HiD Termination Board.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications HiD2030 121495

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionSL1: 1a(-), 1b(-), 2a(+), 2b(+)
Rated voltage20.4 ... 30 V DC bus powered via Termination Board
Rated current60 mA at 24 V, 20 mA output (per channel)
Power dissipation1.05 W at 24 V (per channel)
Input
Connection sidefield side
ConnectionSL2: 5a(+), 5b, 7a(-), 1a(+), 1b, 3b(-)
Input current4 ... 20 mA , current limit 26 mA typ.
Input resistance40 &Omega, , for current source
Ripple10 mV eff
Voltagemin. 15.5 V at 20 mA
Communicationpass-through of HART signal to safe area The current sink terminals 4, 7 and 5, 6 do not pass the HART signal to safe area.
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-), 10a(+), 9a(-)
Load0 ... 650 &Omega,
Output signal4 ... 20 mA or 1 ... 5 V (on 250 &Omega,, 0.1 % internal shunt)
Ripple10 mV eff on a load of 250 &Omega,
Response time70 ms , 10 ... 90 % step change
Signal levelno fault: 1 mA ... 23.5 mA input current fault detection: 24 mA input current
Fault indication output
ConnectionSL1: 6b
Output typeopen collector transistor (common to both channels) fault bus signal, collective error message
Transfer characteristics
Calibrated accuracy< ± 0.1 % of full-scale value (current output)
Influence of temperature< ± 0.01 %/ K
Frequency rangecommunication channel: 0.5 ... 40 kHz within 3 db, (-6 db at 100 kHz), Tx to output and output to Tx, suitable for use with SMART transmitters using HART or similar protocol
Influence of load< ± 0.1 % of full-scale value from 0 ... 650 &Omega,
Linearity< ± 0.05 % of full-scale value
Indicators/settings
Display elementsLEDs
Control elementsDIP-switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006 For further information see system description.
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 140 g
Dimensions18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Mountingon Termination Board
Data for application in connection with hazardous areas
EU-Type Examination CertificateCESI 02 ATEX 086
Marking II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC
CertificatePF 11 CERT 2109 X
Marking II 3G Ex nA IIC T4 Gc [device in zone 2]
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
CSA approval
Control drawing366-005CS-12B (cCSAus)
IECEx approvalIECEx TUN 04.0012
Approved for[Ex ia] IIC