Slots |
Occupied slots | 2 |
Supply |
Connection | backplane bus |
Rated voltage | 5 V DC , only in connection with the power supplies FB92** |
Power dissipation | 1.8 W |
Power consumption | 1.8 W |
Fieldbus interface |
Fieldbus type | PROFIBUS DP/DP-V1 |
PROFIBUS DP | |
| Connection | wired to Ex e terminals via backplane |
| Baud rate | up to 1.5 MBit/s |
| Protocol | PROFIBUS DP/DP V1 read/write services |
Number of stations per bus line | max. 125 (PROFIBUS), max. 119 (service bus) |
Cyclic process data | 240 bytes input and (simultaneously) 240 bytes output |
Number of stations per bus segment | max. 31 (RS-485 standard) |
Number of repeaters between Master and Slave | max. 3 |
Supported I/O modules | all FB remote I/O modules |
Configuration (240 bytes I/O) | Standard: 80 analog, 184 digital
Universal 2I2O: 48 analog, 184 digital
Universal 4I4O: 60 analog, 120 digital |
Bus length | max. 1000 m (FOL, 1.5 MBaud),
max. 1000 m (copper cable, 187.5 kBd),
max. 200 m (copper cable, 1.5 MBd) |
Addressing | via configuration software |
PROFIBUS address | 0 ... 126
(factory standard setting: 126) |
GSE file | CGV61710.gsd/gse |
HART communication | via PROFIBUS or service bus |
Internal bus |
Connection | backplane bus |
Redundancy | via front connector |
Indicators/settings |
LED indication | LED green (power supply): On = operating, fast flash = cold start, slow flash = HCIR loading active
LED red (collective alarm): On = internal fault, flashing = no PROFIBUS connection
LED yellow (operating mode): flashing 1 (1:1 ratio) = active, normal operation, flashing 2 (7:1 ratio) = active, simulation
|
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1 |
Conformity |
Electromagnetic compatibility | NE 21 |
Degree of protection | IEC 60529 |
Fieldbus standard | IEC 61158-2 |
Environmental test | EN 60068-2-14 |
Shock resistance | EN 60068-2-27 |
Vibration resistance | EN 60068-2-6 |
Damaging gas | EN 60068-2-42 |
Relative humidity | EN 60068-2-56 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 95 % non-condensing |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Vibration resistance | frequency range 10 ... 150 Hz, transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g, 10 cycles
frequency range 5 ... 100 Hz, transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g, 90 minutes at each resonance |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description |
Connection | via backplane |
Mass | approx. 750 g |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) |
Data for application in connection with hazardous areas |
EU-type examination certificate | Presafe 19 ATEX 14058U |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013
EN 60079-1:2014
EN 60079-5:2015
EN 60079-7:2015
EN 60079-11:2012 |
International approvals |
ATEX approval | Presafe 19 ATEX 14058U |
IECEx approval | IECEx PRE 19.0013U |
| Approved for | Ex db eb q [ib] IIC Gb
|
General information |
System information | The module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate. |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |