General specifications |
Signal type | Analog input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | SL1: 1a(-), 1b(-), 2a(+), 2b(+) |
Rated voltage | 18 ... 30 V DC bus powered via Termination Board |
Ripple | within the supply tolerance |
Power dissipation | &le, 1.4 W |
Power consumption | &le, 2 W |
Input |
Connection side | field side |
Connection | SL2: 5a(+), 5b, 7a(-), 1a(+), 1b, 3b(-) |
Input signal | 0/4 ... 20 mA , current limit 27 mA |
Input resistance | max. 265 &Omega, SL2: 5b, 7a, 1b, 3b , max. 330 &Omega, SL2: 5a, 7a, 1a, 3b |
Available voltage | &ge, 16 V at 20 mA , SL2: 5a(+), 5b(-), 1a(+), 1b(-) |
Output |
Connection side | control side |
Connection | SL1: 8a(+), 7a(-), 10a(+), 9a(-) |
Output signal | 0/4 ... 20 mA (overload > 25 mA) |
Ripple | max. 50 µ,A rms |
External supply (loop) | 2 ... 30 V DC |
Transfer characteristics |
Deviation | at 20 °C (68 °F), 0/4 ... 20 mA
&le, 10 µ,A incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
| Influence of ambient temperature | &le, 0.25 µ,A/K |
Frequency range | field side into the control side: band width with 1 Vpp signal 0 ... 7.5 kHz (-3 dB)
safe area to hazardous area: band width with 1 VSS signal 0.3 ... 7.5 kHz (-3 dB) |
Settling time | 200 µ,s |
Rise time/fall time | 100 µ,s |
Galvanic isolation |
Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Output/Output | functional insulation, rated insulation voltage 50 V AC |
Indicators/settings |
Display elements | LED |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2012
EN 61326-3-2:2008 |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Relative humidity | 5 ... 90 %, non-condensing up to 35 °C (95 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Mass | approx. 140 g |
Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
Mounting | on Termination Board |
Coding | pin 1 and 3 trimmed
For further information see system description. |
Data for application in connection with hazardous areas |
EU-Type Examination Certificate | CML 17 ATEX 2143X |
| Marking | II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I |
| Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Supply | |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Equipment | SL2: 5a(+), 5b(-), 1a(+), 1b(-) |
| Voltage Uo | 26.2 V |
| Voltage Uq | 27.25 V |
| Current Io | 93 mA |
| Power Po | 634 mW |
Equipment | SL2: 5b(+), 7a(-), 1b(+), 3b(-) |
| Voltage Ui | 30 V |
| Current Ii | 115 mA |
| Power Pi | max 1 W |
| Voltage Uo | 2 V |
| Current Io | 8.5 mA |
| Power Po | 4.3 mW |
Equipment | SL2: 5a(+), 5b, 7a(-), 1a(+), 1b, 3b(-) |
| Voltage Uo | 26.2 V |
| Voltage Uq | 27.25 V |
| Current Io | 115 mA |
| Power Po | 784 mW |
Certificate | CML 17 ATEX 3144X |
| Marking | II 3G Ex ec IIC T4 Gc |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11:2012, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11:2012, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015 |
International approvals |
UL approval | |
| Control drawing | pending |
IECEx approval | IECEx CML 17.0072X |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |