General specifications |
Signal type | Analog input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 3 |
Supply |
Connection | SL1: 1a(-), 1b(-), 2a(+), 2b(+) |
Rated voltage | 19 ... 30 V DC bus powered via Termination Board |
Ripple | &le, 10 % |
Rated current | &le, 50 mA |
Power dissipation | &le, 800 mW |
Power consumption | &le, 1.2 W |
Input |
Connection side | field side |
Connection | SL2: 5a(+), 1b(-), 5a(+), 5b(-) |
Input signal | 4 ... 20 mA , limited to approx. 27 mA reverse polarity protected |
Line fault detection | downscaling &le, 3 mA , upscaling &ge, 22 mA |
Voltage drop | approx. 5 V on SL2: 5a(+), 1b(-) |
Available voltage | &ge, 15 V at 20 mA on SL2: 5a(+), 5b(-) |
Output |
Connection side | control side |
Connection | SL1: 8a(+), 7a(-) |
Load | 0 ... 300 &Omega, (source mode) |
Output signal | 4 ... 20 mA or 1 ... 5 V (on 250 &Omega,, 0.1 % internal shunt)
4 ... 20 mA (sink mode), operating voltage 16 ... 28 V |
Ripple | 20 mV rms |
Fault indication output |
Connection | SL1: 6b |
Output type | open collector transistor (internal fault bus) |
Transfer characteristics |
Deviation | at 20 °C (68 °F)
&le, ± 20 µ,A incl. calibration, linearity, hysteresis, loads and supply voltage fluctuations (source mode and sink mode 4 ... 20 mA)
&le, 10 mV incl. calibration, linearity, hysteresis and fluctuations of supply voltage (source mode 1 ... 5 V) |
| Influence of ambient temperature | < 2 µ,A/K (0 ... 70 °C (32 ... 158 °F)), < 4 µ,A/K (-20 ... 0 °C (-4 ... 32 °F)) (source mode and sink mode 4 ... 20 mA)
< 0.5 mV/K (0 ... 70 °C (32 ... 158 °F)), < 1 mV/K (-20 ... 0 °C (-4 ... 32 °F)) (source mode 1 ... 5 V) |
Frequency range | field side into the control side: bandwidth with 1 mApp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) |
Settling time | &le, 200 ms |
Rise time/fall time | &le, 20 ms |
Galvanic isolation |
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Output/power supply | Basic isolation acc. to EN 61010-1 rated insulation voltage &le, 50 V |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP-switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2017
For further information see system description. |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Mass | approx. 100 g |
Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
Mounting | on Termination Board |
Coding | pin 1 and 3 trimmed
For further information see system description. |
Data for application in connection with hazardous areas |
EU-type examination certificate | CESI 10 ATEX 063 |
| Marking | II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I |
| Input | Ex ia |
Supply | |
| Maximum safe voltage | 253 V AC (Attention! Um is no rated voltage.) |
Equipment | SL2: 5a(+), 5b(-) |
| Voltage Uo | 25.2 V |
| Current Io | 100 mA |
| Power Po | 630 mW |
Equipment | SL2: 5a(+), 1b(-) |
| Voltage Ui | < 30 V |
| Current Ii | < 128 mA |
| Voltage Uo | 7.2 V |
| Current Io | 100 mA |
| Power Po | 25 mW |
Certificate | CESI 19 ATEX 016 X |
| Marking | II 3G Ex ec IIC T4 Gc |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015 |
International approvals |
UL approval | E106378 |
| Control drawing | 116-0376 (cULus) |
IECEx approval | |
| IECEx certificate | IECEx CES 10.0021X |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |