Application |
---|
Application | Sum function, for general industrial use |
Installation | pipe connection with adapter |
Medium | Conductive liquids, Water, water-based liquids |
Medium note | Conductivity: ? 20 µS/cm | Viscosity: < 70 mm?/s (40 °C) |
|
Measured medium temperature [°C] | -10…70 |
Pressure strength [bar] | 16 |
MAWP (for use according to CRN) [bar] | 17.7 |
Electronic data |
---|
Operating voltage [V] | 18…30 DC, (according to EN 50178 SELV/PELV ) |
Current consumption [mA] | 95, (24 V) |
Min. insulation resistance [M?] | 100, (500 V DC) |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 5 |
Inputs/outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2, Number of analog outputs: 1 |
Inputs |
---|
Inputs | counter reset |
Outputs |
---|
Total number of outputs | 2 |
Output signal | switching signal, analog signal, pulse signal, IO-Link, (configurable) |
Electrical version | PNP/NPN |
Number of digital outputs | 2 |
Output signal function | normally open / normally closed, (parameterizable) |
Max. voltage drop DC switching output [V] | 2 |
DC switching output load current [mA] | 200 |
Number of analog outputs | 1 |
Analog current output [mA] | 4…20, (scalable) |
Max. load [?] | 500 |
Analog voltage output [V] | 0…10, (scalable) |
Min. load resistance [?] | 2000 |
Pulse output | Flowmeter |
Short-circuit protection | yes |
Short-circuit protection type | clocked |
Overcurrent protection | yes |
Measurement/setting range |
---|
Range measurements | 0.1…25 l/min | 0.005…1.5 m?/h |
|
Display range | -30…30 l /min | -1.8…1.8 m?/h |
|
Resolution | |
Setting point SP | 0.25…25 l/min | 0.015…1.5 m?/h |
|
Reset point rP | 0.1…24.9 l/min | 0.005…1.495 m?/h | < /tbody>
|
Analog start point nala, ASP | |
Analogue Endpoint, AEP | |
Step width | |
Momentary flow control |
---|
Impulse value | 0.00001…30 000 m? |
Pulse length [s] | 0.01…2 |
Temperature control |
---|
Measuring range [°C] | -20…80 |
Resolution [°C] | 0.2 |
Setting point SP [°C] | -19, 2…80 |
Reset point rP [°C] | -19.6…79.6 |
Analog start point [°C] | -20…60 |
Analog end point [°C] | 0 …80 |
In steps of [°C] | 0.2 |
Accuracy/Uncertainty < /th> |
---|
Flow rate control |
---|
Accuracy (in measuring range) | ± (0, 8% MW + 0.5% MEW) |
Repeatability | ± 0.2% MEW |
< th colspan=2>Temperature control
Accuracy [K] | ± 2.5 (Q > 1 l/min) |
Response Time |
---|
Flow Rate Control |
---|
Response Time [s] | 0.15, (dAP = 0) |
Programmable delay time dS, dr [s] | 0…50 | 0…50 | 0…50 | | |
Switching output damping dAP [s] | 0…5 |
Temperature monitoring th> |
---|
Dynamics of response T05 / T09 [s] | T09 = 20 (Q > 1 l/min) |
Software / Programming |
---|
Parameter selection | Flow rate control, flow meter, preset counter, Temperature control, hysteresis/window, normally open/normally closed, switching logic , current output/voltage output/pulse output, Start delay, display can be switched off, Display |
Interfaces |
---|
Communication interface | IO-Link |
Transmission method | COM2 (38.4 kBaud) |
IO-Link test | 1.1 |
SDCI standard | IEC 61131-9 |
IO-Link device ID | 569 / 00 02 39 h |
Profiles | Smart Sensor: Process Data Variable, Device Identification, Device Diagnosis |
SIO Mode | Yes |
Desired port type | A |
Analog operating data e | 3 |
Binary operating data | 2 |
Min. cycle time [ms] | 5 |
Operating conditions |
---|
Ambient temperature [°C ] | -10…60 |
Storage temperature [°C] | -25…80 |
Degree of protection | IP 67 | Tests / approvals |
---|
EMC | |
Impact resistance | DIN IEC 68-2-27 | 20 g ( 11 ms) |
|
Vibration resistance | DIN IEC 68-2-6 | 5 g (10…2000 Hz) |
|
MTTF [years] | 145 |
Pressure Equipment Directive | Good engineering practice, can use for fluid group 2, fluid group 1 on request |
Mechanical data |
---|
Be with [g] | 548 |
Material | stainless steel steel (1.4404 / 316L), PBT-GF20, PC, FKM, TPE medium | stainless steel steel (1.4404 / 316L), PEEK, EPDM |
Process connection | G 1/2 DN15 threaded connection Flat seal |
Displays / Controls |
---|
Display | Display | 6 x LED, green (l/min, m?/h, l, m?, 10?, °C) | Output status | 2 x LED, yellow | Measured values | alphanumeric display, 4 digits | programming | alphanumeric display, 4 digits |
|
Notes< /th> |
---|
Notes | MW = Measured value | MEW = Upper limit of measuring range |
|
Pack quantity | 1 piece |
electrical connection |
---|
Connection | Connector: 1 x M12, Contacts: gold-plated |
Diagrams and Graphs |
---|
Pressure Loss | dP | Pressure loss |
---|
Q | volumetric consumption |
---|
|
---|