General specifications |
Switching function | Normally closed (NC) |
Output type | NAMUR with safety function |
Slot width | 3.5 mm |
Depth of immersion (lateral) | 5 ... 7 typ. 6 mm |
Reference target | 10 x 7 x 0.3 mm3, Al |
Safety Integrity Level (SIL) | up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1.
Consider the exida Functional Safety Assessment document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation. |
Output type | 2-wire |
Nominal ratings |
Nominal voltage | 8.2 V |
Switching frequency | 0 ... 3000 Hz |
Hysteresis | with NAMUR switch amplifier: 0.045 mm (e. g. Pepperl+Fuchs KCD2-SR-Ex1.LB)
with safety switch amplifier 0.025 mm (e. g. Pepperl+Fuchs KFD2-SH-Ex1) |
Suitable for 2:1 technology | yes , with reverse polarity protection diode |
Rate of current rise | -4.5 mA / mm |
Current consumption | |
| Measuring plate not detected | &ge, 3 mA |
| Measuring plate detected | 0.2 ... 1 mA |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 3 |
MTTFd | 11800 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives |
Standard conformity | |
| NAMUR | EN 60947-5-6:2000
IEC 60947-5-6:1999 |
| Standards | EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012 |
Approvals and certificates |
EAC conformity | TR CU 012/2011 |
FM approval | |
| Control drawing | 116-0165 |
UL approval | cULus Listed, General Purpose |
| Ordinary Location | E87056 |
| Hazardous Location | E501628 |
| Control drawing | 116-0454 |
CCC approval | CCC approval / marking not required for products rated &le,36 V |
Ambient conditions |
Ambient temperature | -50 ... 100 °C (-58 ... 212 °F)
Safety application: -40 ... 100°C |
Mechanical specifications |
Connection type | flexible leads LiY , 500 mm |
Core cross-section | 0.14 mm2 |
Housing material | PBT |
Degree of protection | IP67 |
Note | adjustable stop
Security relevant only up to -40°C |
Data for application in connection with hazardous areas |
Equipment protection level | Ga , Gb , Gc (ic) , Da , Mb |
Equipment protection level Ga |
Type of protection | intrinsic safety |
CE marking | [*PD-Z02585A*] |
Certificates | |
| Appropriate type | SJ3,5-SN... |
| ATEX certificate | PTB 00 ATEX 2049 X |
| ATEX marking | II 1G Ex ia IIC T6...T1 Ga |
| Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
| IECEx certificate | IECEx PTB 11.0092X |
| IECEx marking | Ex ia IIC T6...T1 Ga |
| Standards | IEC 60079-0:2011 , IEC 60079-11:2011 |
Effective internal capacitance | max. 30 nF
A cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H
A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values. |
| for ATEX | at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 56 °C (132.8 °F)
T5 : 68 °C (154.4 °F)
T4 : 96 °C (204.8 °F)
T3 : 96 °C (204.8 °F)
T2 : 96 °C (204.8 °F)
T1 : 96 °C (204.8 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 49 °C (120.2 °F)
T5 : 61 °C (141.8 °F)
T4 : 89 °C (192.2 °F)
T3 : 89 °C (192.2 °F)
T2 : 89 °C (192.2 °F)
T1 : 89 °C (192.2 °F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 28 °C (82.4 °F)
T5 : 40 °C (104 °F)
T4 : 68 °C (154.4 °F)
T3 : 68 °C (154.4 °F)
T2 : 68 °C (154.4 °F)
T1 : 68 °C (154.4 °F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 13 °C (55.4 °F)
T5 : 25 °C (77 °F)
T4 : 53 °C (127.4 °F)
T3 : 53 °C (127.4 °F)
T2 : 53 °C (127.4 °F)
T1 : 53 °C (127.4 °F) |
| for IECEx | at Ui = 16 V , Ii = 25 mA 34 mW ,
T6 : 73 °C (163.4 °F)
T5 : 88 °C (190.4 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 66 °C (150.8 °F)
T5 : 81 °C (177.8 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 45 °C (113 °F)
T5 : 60 °C (140 °F)
T4 : 89 °C (192.2 °F)
T3 : 89 °C (192.2 °F)
T2 : 89 °C (192.2 °F)
T1 : 89 °C (192.2 °F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 30 °C (86 °F)
T5 : 45 °C (113 °F)
T4 : 74 °C (165.2 °F)
T3 : 74 °C (165.2 °F)
T2 : 74 °C (165.2 °F)
T1 : 74 °C (165.2 °F) |
Equipment protection level Gb |
Type of protection | intrinsic safety |
CE marking | [*PD-Z02585A*] |
Certificates | |
| Appropriate type | SJ3,5-SN... |
| ATEX certificate | PTB 00 ATEX 2049 X |
| ATEX marking | II 1G Ex ia IIC T6&hellip,T1 Ga |
| Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
| IECEx certificate | IECEx PTB 11.0092X |
| IECEx marking | Ex ia IIC T6...T1 Ga |
| Standards | IEC 60079-0:2011 , IEC 60079-11:2011 |
Effective internal capacitance | max. 30 nF
A cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H
A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 73 °C (163.4 °F)
T5 : 88 °C (190.4 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 66 °C (150.8 °F)
T5 : 81 °C (177.8 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 45 °C (113 °F)
T5 : 60 °C (140 °F)
T4 : 89 °C (192.2 °F)
T3 : 89 °C (192.2 °F)
T2 : 89 °C (192.2 °F)
T1 : 89 °C (192.2 °F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 30 °C (86 °F)
T5 : 45 °C (113 °F)
T4 : 74 °C (165.2 °F)
T3 : 74 °C (165.2 °F)
T2 : 74 °C (165.2 °F)
T1 : 74 °C (165.2 °F) |
Equipment protection level Gc (ic) |
Type of protection | intrinsic safety |
CE marking | [*PD-Z02586A*] |
Certificates | |
| ATEX certificate | PF 13 CERT 2895 X |
| ATEX marking | II 3G Ex ic IIC T6&hellip,T1 Gc |
| Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
Effective internal capacitance | max. 30 nF
A cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H
A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 20 V , Ii = 25 mA , Pi = 34 mW ,
T6 : 70 °C (158 °F)
T5 : 85 °C (185 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 20 V , Ii = 25 mA , Pi = 64 mW ,
T6 : 66 °C (150.8 °F)
T5 : 81 °C (177.8 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at Ui = 20 V , Ii = 52 mA , Pi = 169 mW ,
T6 : 45 °C (113 °F)
T5 : 60 °C (140 °F)
T4 : 89 °C (192.2 °F)
T3 : 89 °C (192.2 °F)
T2 : 89 °C (192.2 °F)
T1 : 89 °C (192.2 °F)
at Ui = 20 V , Ii = 76 mA , Pi = 242 mW ,
T6 : 30 °C (86 °F)
T5 : 45 °C (113 °F)
T4 : 74 °C (165.2 °F)
T3 : 74 °C (165.2 °F)
T2 : 74 °C (165.2 °F)
T1 : 74 °C (165.2 °F) |
Equipment protection level Da |
Type of protection | intrinsic safety |
CE marking | [*PD-Z02585A*] |
Certificates | |
| Appropriate type | SJ3,5-SN... |
| ATEX certificate | PTB 00 ATEX 2049 X |
| ATEX marking | II 1D Ex ia IIIC T135°C Da |
| Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
| IECEx certificate | IECEx PTB 11.0092X |
| IECEx marking | Ex ia IIIC T135°C Da |
| Standards | IEC 60079-0:2011 , IEC 60079-11:2011 |
Effective internal capacitance | max. 30 nF , a cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H
A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 89 °C (192.2 °F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 74 °C (165.2 °F) |
Equipment protection level Mb |
Type of protection | intrinsic safety |
Certificates | |
| Appropriate type | SJ3,5-SN... |
| IECEx certificate | IECEx PTB 11.0092X |
| IECEx marking | Ex ia I Mb |
| Standards | IEC 60079-0:2011 , IEC 60079-11:2011 |
Effective internal capacitance | max. 30 nF
A cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H
A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F)
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F)
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 89 °C (192.2 °F)
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 74 °C (165.2 °F) |
General information |
Use in the hazardous area | see instruction manuals |