General specifications |
Signal type | Analog input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | Power Rail or terminals 9+, 10- |
Rated voltage | 18 ... 30 V DC |
Ripple | within the supply tolerance |
Power dissipation | approx. 1.4 W at 20 mA transfer current, 250 &Omega, in both outputs |
Power consumption | 2 W |
Input |
Connection side | field side |
Connection | terminals 1+, 2- (sink), 3+, 4- (source) |
Input signal | 0/4 ... 20 mA |
Voltage drop | terminals 3, 4: &le, 6.1 V at 20 mA |
Short-circuit current | terminals 1+, 2-: 25 mA |
Input resistance | terminals 1+, 2-: max. 500 &Omega, (BRAIN)
(250 &Omega, load) |
Available voltage | terminals 1+, 2-: &ge, 16 V at 20 mA , &ge, 18.5 V at 4 mA |
Output |
Connection side | control side |
Connection | source: terminals 5-, 6+, 7-, 8+
sink: terminals 5+, 6-, 7+, 8- |
Load | channel 1: 0 ... 500 &Omega, (20 mA)/> 1 M&Omega, (5 V)
channel 2: 0 ... 500 &Omega, (20 mA)/> 1 M&Omega, (5 V) |
Output signal | 0/4 ... 20 mA or 0/1 ... 5 V |
Ripple | max. 50 µ,A rms |
Transfer characteristics |
Deviation | Iout < 20 µ,A (0.1 %), Vout < 10 mV (0.2 %) incl. calibration, linearity, hysteresis and fluctuation of supply voltage, at 20 °C (68 °F), 0/4 ... 20 mA, 0/1 ... 5 V |
| Influence of ambient temperature | current output: 0.25 µ,A/K
voltage output: 80 µ,V/K |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 6 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 6 kHz (-3 dB) |
Settling time | 6 ms |
Rise time/fall time | 2 ms |
Galvanic isolation |
Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Output/Output | functional insulation, rated insulation voltage 50 V AC |
Indicators/settings |
Display elements | LED |
Control elements | DIP-switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2012
EN 61326-3-2:2008 |
Degree of protection | IEC 60529:2001 |
Protection against electrical shock | UL 61010-1:2012 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Dimensions | 12.5 x 114 x 122 mm (0.5 x 4.5 x 4.8 inch) , housing type A2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | BASEEFA 13 ATEX 0077 X |
| Marking | II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I |
| Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Supply | |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Equipment | terminals 1+, 2- |
| Voltage Uo | 25.2 V |
| Voltage Uq | 28.2 V |
| Current Io | 93 mA |
| Power Po | 656 mW |
| Internal capacitance Ci | 10 nF |
| Internal inductance Li | 0 mH |
Equipment | terminals 3+, 4- |
| Voltage Ui | 30 V |
| Current Ii | 115 mA |
| Power Pi | 700 mW |
| Voltage Uo | 5 V |
| Current Io | 6.8 mA |
| Power Po | 1.6 mW |
Output | |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Certificate | BASEEFA 13 ATEX 0078 X |
| Marking | II 3G Ex nA II T4 Gc [device in zone 2] |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
UL approval | |
| Control drawing | 116-0380 (cULus) |
IECEx approval | IECEx BAS 13.0043X |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General information |
Note | Both output loads must be connected to ensure complete and correct operation within the technical specification. |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Accessories |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03) |