Supply of spare parts for industrial enterprises around the world
Home Brands Pepperl+Fuchs 180491 NCB40-FP-N0-P1-V1

Pepperl+Fuchs NCB40-FP-N0-P1-V1 180491

Inductive sensor NCB40-FP-N0-P1-V1 Pepperl+Fuchs 180491
Manufacturer
Pepperl+Fuchs
Name
NCB40-FP-N0-P1-V1
Part number
180491
Country
Germany
Type
Inductive sensor
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


Order Pepperl+Fuchs 180491 Spare Parts Online for Enhanced Efficiency

For industries seeking reliable components, Pepperl+Fuchs 180491 Industrial parts are the ideal choice. Built with precision and innovation, these Pepperl+Fuchs 180491 spare parts optimize industrial operations across USA.

What Makes 2technologie Stand Out?

  • Comprehensive Options: A full range of Pepperl+Fuchs 180491 spares for all applications.

  • Swift Delivery: Quick access to Pepperl+Fuchs 180491 spare parts near me or online.

  • Cost-Effective Solutions: Quality Pepperl+Fuchs 180491 Industrial products at the best prices.

  • Proven Expertise: A trusted provider of Pepperl+Fuchs 180491 Industrial components.

Order Pepperl+Fuchs 180491 spare parts today and experience the 2technologie difference!

Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications NCB40-FP-N0-P1-V1 180491

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance40 mm
Installationflush
Assured operating distance0 ... 32 mm
Actual operating distance36 ... 44 mm typ. 40 mm
Reduction factor rAl 0.35
Reduction factor rCu 0.35
Reduction factor r304 0.8
Output type2-wire
Nominal ratings
Installation conditions
F100 mm
Nominal voltage8.2 V (Ri approx. 1 k&Omega,)
Switching frequency0 ... 80 Hz
Hysteresis0 ... 5 typ. 3 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionyes
Current consumption
Measuring plate not detected&ge, 3 mA
Measuring plate detected&le, 1 mA
Time delay before availability&le, 20 ms
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd2368 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
Electromagnetic compatibilityNE 21:2007
StandardsEN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Approvals and certificates
EAC conformityTR CU 012/2011
FM approval
Control drawing116-0165
UL approval
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0451
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated &le,36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Storage temperature-40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection typeConnector plug M12 x 1 , 4-pin
Housing materialPBT
Sensing facePBT
Housing basePBT
Degree of protectionIP67
Equipment protection level Ga
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNCB40-FP-N0..
Effective internal capacitancemax. 220 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 360 µ,H , a cable length of 10 m is considered.
Highest permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1.
Equipment protection level Gb
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNCB40-FP-N0..
Effective internal capacitancemax. 220 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 360 µ,H , a cable length of 10 m is considered.
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Equipment protection level Da
CE marking[*PD-Z02585A*]
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNCB40-FP-N0..
Effective internal capacitancemax. 220 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 360 µ,H , a cable length of 10 m is considered.
General information
Use in the hazardous areasee instruction manuals
Category1G, 2G, 1D