General specifications |
Signal type | Analog input |
Supply |
Connection | Power Rail or terminals 11+, 12- |
Rated voltage | 20 ... 35 V DC |
Ripple | within the supply tolerance |
Rated current | < 20 mA |
Input |
Connection side | field side |
Connection | terminals 4+, 5- |
Input resistance | min. 10 M&Omega, |
Transmission range | 0 ... 12 V |
Offset voltage/current | < 2 mV / < 7 nA |
Output |
Connection side | control side |
Connection | terminals 7-, 8+ |
Voltage | 0 ... 12 V |
Output resistance | max. 20 &Omega, |
Transfer characteristics |
Cut-off frequency | 1.2 kHz (-3 dB) |
Deviation | |
| After calibration | ± 5 mV at 20 °C (68 °F) |
| Influence of ambient temperature | &le, 0.005 % of range per K |
Rise time | &le, 0.4 ms |
Galvanic isolation |
Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Indicators/settings |
Display elements | LED |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21 |
Degree of protection | IEC 60529 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | BAS 01 ATEX 7262 |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le, Tamb &le, 60 °C) , [circuit(s) in zone 0/1/2] |
| Voltage | 18 V |
| Current | 4.2 mA |
| Power | 19 mW |
Supply | |
| Maximum safe voltage | 250 V (Attention! The rated voltage is lower.) |
Output | |
| Maximum safe voltage | 250 V (Attention! The rated voltage is lower.) |
Certificate | BASEEFA 10 ATEX 0079X |
| Marking | II 3G Ex ec IIC T4 Gc [device in zone 2] |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018 |
International approvals |
FM approval | |
| Control drawing | 116-0129 |
UL approval | |
| Control drawing | 116-0173 (cULus) |
CSA approval | |
| Control drawing | 116-0132 |
IECEx approval | |
| IECEx certificate | IECEx BAS 10.0040X |
| IECEx marking | Ex ec IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Accessories |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03) |