Supply of spare parts for industrial enterprises around the world

Pepperl+Fuchs Z787.H.F 072179

Module Z787.H.F Pepperl+Fuchs 072179
Manufacturer
Pepperl+Fuchs
Name
Z787.H.F
Part number
072179
Country
Germany
Type
Module
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


The Zener Barrier prevents the transfer of unacceptably high energy from the safe area into the hazardous area. The zener diodes in the Zener Barrier are connected in the reverse direction. The breakdown voltage of the diodes is not exceeded in normal operation. If this voltage is exceeded, due to a fault in the safe area, the diodes start to conduct, causing the fuse to blow. The Zener Barrier has a positive polarity, i. e. the anodes of the zener diodes are grounded. Additionally this Zener Barrier is equipped with a replaceable fuse. This high power version has a smaller serial resistance and therefore provides higher voltage to the field device. The Zener Barrier is for evaluation of signals from the hazardous area. The diodes of diode return prevent a current into the hazardous area, therefore the current assumption for intrinsic safety calculations is zero. Depending on the application, increased or decreased intrinsic safety parameters apply for serial or parallel connection. For the detailed parameters refer to the Zener Barrier certificate. Application examples can be found in the system description of the Zener Barriers.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications Z787.H.F 072179

General specifications
TypeDC version, positive polarity
Electrical specifications
Nominal resistance240 &Omega,
Series resistancemax. 273 &Omega,
Fuse rating50 mA
Hazardous area connection
Connectionterminals 1, 2, 3, 4
Safe area connection
Connectionterminals 5, 6, 7, 8
Working voltage
Supply loopmax. 27 V
Measurement loopmax. 26.5 V at 10 µ,A
Conformity
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 70 °C (-13 ... 158 °F)
Relative humiditymax. 75 % , without condensation
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Core cross-sectionmax. 2 x 2.5 mm2
Massapprox. 150 g
Dimensions12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch)
Construction typemodular terminal housing , see system description
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateBAS 00 ATEX 7096
Marking II (1)GD, [Ex ia Ga] IIC, [Ex ia Da] IIIC, (-20 °C &le, Tamb &le, 60 °C) [circuit(s) in zone 0/1/2]
Voltage28 V
Current120 mA
Power830 mW
Supply
Maximum safe voltage250 V
Series resistancemin. 235.2 &Omega,
CertificateTÜV 99 ATEX 1484 X
Marking II 3G Ex nA II T4 [device in zone 2]
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0118
UL approval
Control drawing116-0355 (cULus)
IECEx approvalIECEx BAS 18.0033
Approved for[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.