Supply of spare parts for industrial enterprises around the world
Home Brands Euchner 090819 ESM-BT411

Euchner ESM-BT411 090819

 ESM-BT411 Euchner 090819
Manufacturer
Euchner
Name
ESM-BT411
Part number
090819
Country
Germany
Sale of any product from the Euchner catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Euchner (official website: www.euchner.de/en-us/). We sell only certified goods and give an official guarantee from the manufacturer Euchner


Order Euchner 090819 Spare Parts Online for Enhanced Efficiency

For industries seeking reliable components, Euchner 090819 Industrial parts are the ideal choice. Built with precision and innovation, these Euchner 090819 spare parts optimize industrial operations across USA.

What Makes 2technologie Stand Out?

  • Comprehensive Options: A full range of Euchner 090819 spares for all applications.

  • Swift Delivery: Quick access to Euchner 090819 spare parts near me or online.

  • Cost-Effective Solutions: Quality Euchner 090819 Industrial products at the best prices.

  • Proven Expertise: A trusted provider of Euchner 090819 Industrial components.

Order Euchner 090819 spare parts today and experience the 2technologie difference!

Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications ESM-BT411 090819

  • Usage up to category 4 according to EN ISO 13849-1
  • LED status indicators
  • 1-channel or 2-channel control
  • 4 redundant safety contacts of which 2 contacts time-delayed
  • Delay time-range 1 s - 30 s
  • Short circuit and earth fault/ground fault monitoring
  • 24 V DC for ESM-BT411
Relay outputsThe outputs are electrically decoupled and of redundant design. Connection optionsBy using suitable wiring the following functions can be selected:
  • Relay start with automatic start, a start button or a monitored start button
  • Monitoring of downstream relays or contactors
  • Simultaneity monitoring to monitor safety components over time
  • Relay start using a monitored start button
  • Short circuit monitoring to detect short circuits between the connection cables and to shut down the outputs or prevent relay starting if necessary
  • Earth fault/ground fault monitoring to detect short circuits between the connection cables and earth or ground and to shut down the outputs or prevent relay starting if necessary.
Time-delayed shutdownThe release time for the time-delay contacts can be set as required using a potentiometer on the safety relay. Dimension drawing ESM-BT411 Dimension drawingESM-BT411 Technical dataApprovals Mechanical values and environment
Housing material Polyamide PA6.6
Weight
Net 0,25 kg
Ambient temperature -15 ... 40 °C
Degree of protection IP20
Mechanical life
operating cycles 10 x 106
Contact material AgSnO2
Mounting method Mounting rail 35mm according to DIN EN 60715 TH35
Connection Connection terminals
Length of control cable
With conductor cross-section 0.75mm2 1000 m
Safety contacts 13/14, 23/24, 37/38, 47/48
Number of NO contacts 4
Electrical connection ratings
Operating voltage
AC/DC 24 V -10% ... +10%
Power consumption (apparent power)
At 24V AC 5,3 VA
Rated insulation voltage Ui 250 V
Rated impulse withstand voltage Uimp
Leakage path/air gaps 4 kV
Reverse polarity protection
On version UB =24V DC
Rated supply frequency 50 ... 60 Hz
Power consumption
at 24V DC 4,7 W
Degree of contamination (external, according to EN 60947-1) 2
Connection cross-section 0,14 ... 2,5 mm? Connection terminal (size)
Test voltage
Control system/contacts 2,5 kV
Control voltage
On S11 24 V 18,6 ... 26 V Start button
Control current 190 mA
Drop-out delay max.20 ms Emergency stop
LED indicator 4 status displays (green) for relays K1, K2, K3, K4
Safety contacts 13/14, 23/24, 37/38, 47/48
Type of output
NO Relay contacts floating and positively driven (redundant)
Switching voltage
AC max.250 V
DC max.50 V
Switching current min.5 mA at 24V
Cumulative current max.15 A For all contacts
Fusing
External contact fuses (safety circuit) according to IEC 60269-1 10A gG (T6A / F8A)
Utilization category according to EN 60947-5-1
AC-15 3A, 250V
DC-13 3A, 24V
AC-12 8A ohmic load, 250V
DC-12 8A ohmic load, 50V
Breaking capacity according to UL 8A 250V AC / 3A 24V DC per contact
Switching characteristics 2 safety contacts non-delayed, 2 safety contacts time-delayed
Delay time
Continuously adjustable 1 ... 30 s
Other
In compliance with EN 60439-1: 1999 + A1: 2004, EN 60947-1: 2007, EN 60947-5-1: 2004, EN 60947-7-1: 2002, EN 61000-6-2: 2005, EN 61000-6-3: 2007, EN ISO 13849-1: 2015, EN 62061: 2005 + AC: 2010 + A1: 2013 + A2: 2015, EN 60204-1: 2007
Reliability values according to EN ISO 13849-1
Performance Level PL e
Category
Safety contacts time-delay 3
Safety contacts non-time-delay 4
PFHD
Safety contacts time-delay 8.84 x 10-8
Safety contacts non-time-delay 4.22 x 10-8
Number of switching cycles
? 1 A at 24 V DC max.350000 1/Jahr
? 2 A at 24 V DC max.100000 1/Jahr
? 0.1 A at 24 V DC max.500000 1/Jahr
Mission time 20 y