Supply of spare parts for industrial enterprises around the world

Polylux TIN

Transformer TIN Polylux
Manufacturer
Polylux
Name
TIN
Country
Spain
Type
Transformer
Sale of any product from the Polylux catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Polylux (official website: www.polylux.com). We sell only certified goods and give an official guarantee from the manufacturer Polylux


The short circuit on terminals or the connection to earth can be achieved by the double fast-on or connecting two wires on the same terminal.

Protection transformers

The C.T. when used as a current generator for protection relays has electrical characteristics which differ from those of the measuring transformer.

In fact, the measuring C.T. is expected to give a saturation of the magnetic circuit with 5P in primary currents, while in the case of protective C.T., it is necessary for the secondary current value to follow the increase in the primary current up to 10-15-20In, so as to guarantee the intervention of the relay in the case of unforeseen breakdown current.

It is important not to load the C.T. with a P performance which is greater than that indicated, so as not to modify the saturation value of the C.T.

P=R∗I2

P = Load on the C.T.

R = Resistance of the relay and resistance of the cables

I = Nominal secondary current of the C.T.

Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications TIN

ModelTIN400ATIN500ATIN600ATIN800ATIN1000ATIN1200ATIN1500A
LBL_INT_E400 A500 A600 A800 A1000 A1200 A1500 A
LBL_INT_S5 A5 A5 A5 A5 A5 A5 A
Class0,5 / 1 / 30,5 / 1 / 30,5 / 1 / 30,5 / 1 / 30,5 / 1 / 30,5 / 1 / 30,5 / 1 / 3
Rating1,5 VA / 3 VA / 10 VA2,5 VA / 5 VA / 15 VA2,5 VA / 5 VA / 17,5 VA3 VA / 7 VA / 18 VA5 VA / 9 VA / 20 VA6 VA / 11 VA / 24 VA8 VA / 17 VA / 30 VA
Frequency50 - 60 Hz50 - 60 Hz50 - 60 Hz50 - 60 Hz50 - 60 Hz50 - 60 Hz50 - 60 Hz
Thermic short circuit current40 IpN 1 seg.40 IpN 1 seg.20 In20 In20 In20 In20 In
Dynamic short circuit current2,5 I th 1 seg.2,5 I th 1 seg.2,5 I th 1 seg.2,5 I th 1 seg.2,5 I th 1 seg.2,5 I th 1 seg.2,5 I th 1 seg.
Permanent overloading120% Icth120% Icth120% Icth120% Icth120% Icth120% Icth120% Icth
InsulationIn air, Class EIn air, Class EIn air, Class EIn air, Class EIn air, Class EIn air, Class EIn air, Class E
Test voltage3kv (50Hz) 1 min.3kv (50Hz) 1 min.3kv (50Hz) 1 min.3kv (50Hz) 1 min.3kv (50Hz) 1 min.3kv (50Hz) 1 min.3kv (50Hz) 1 min.
Protection degreeIP30IP30IP30IP30IP30IP30IP30
Ambient temperature-20ºC a 40ºC-20ºC a 40ºC-20ºC a 40ºC-20ºC a 40ºC-20ºC a 40ºC-20ºC a 40ºC-20ºC a 40ºC
StandardsEN 60044-1EN 60044-1EN 60044-1EN 60044-1EN 60044-1EN 60044-1EN 60044-1
MountingScrewsScrewsScrewsScrewsScrewsScrewsScrews
Weight1,3 kg1,3 kg1,3 kg1,3 kg1,8 kg1,8 kg1,8 kg
Dimensions (AxBxCxDxE)114x50x145 mm114x50x145 mm114x50x145 mm144x50x185 mm144x50x185 mm144x50x185 mm144x50x185 mm