Supply of spare parts for industrial enterprises around the world

Polylux TIB

Transformer TIB Polylux
Manufacturer
Polylux
Name
TIB
Country
Spain
Type
Transformer
Sale of any product from the Polylux catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Polylux (official website: www.polylux.com). We sell only certified goods and give an official guarantee from the manufacturer Polylux


The short circuit on terminals or the connection to earth can be achieved by the double fast-on or connecting two wires on the same terminal.

Protection transformers

The C.T. when used as a current generator for protection relays has electrical characteristics which differ from those of the measuring transformer.

In fact, the measuring C.T. is expected to give a saturation of the magnetic circuit with 5P in primary currents, while in the case of protective C.T., it is necessary for the secondary current value to follow the increase in the primary current up to 10-15-20In, so as to guarantee the intervention of the relay in the case of unforeseen breakdown current.

It is important not to load the C.T. with a P performance which is greater than that indicated, so as not to modify the saturation value of the C.T.

P=R∗I2

P = Load on the C.T.

R = Resistance of the relay and resistance of the cables

I = Nominal secondary current of the C.T.

Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications TIB

ModelTIB10ATIB15ATIB25A
LBL_INT_E10 A15 A25 A
LBL_INT_S5 A5 A5 A
Class1/31/31/3
Rating3 VA / 6 VA3 VA / 6 VA3 VA / 6 VA
Frequency50 - 60 Hz50 - 60 Hz50 - 60 Hz
Thermic short circuit current40 IpN 1 seg.40 IpN 1 seg.40 IpN 1 seg.
Dynamic short circuit current2,5 I th 1 seg.2,5 I th 1 seg.2,5 I th 1 seg.
Permanent overloading120% Icth120% Icth120% Icth
InsulationIn air, Class EIn air, Class EIn air, Class E
Test voltage3kv (50Hz) 1 min.3kv (50Hz) 1 min.3kv (50Hz) 1 min.
Protection degreeIP30IP30IP30
Ambient temperature-20ºC a 40ºC-20ºC a 40ºC-20ºC a 40ºC
StandardsEN 60044-1EN 60044-1EN 60044-1
MountingScrews and DIN railScrews and DIN railScrews and DIN rail
Weight0,4 kg0,4 kg0,4 kg