Slots |
Occupied slots | 2 |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | backplane bus |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** |
Power dissipation | 2.35 W |
Power consumption | 2.35 W |
Internal bus |
Connection | backplane bus |
Interface | manufacturer-specific bus to standard com unit |
Digital output |
Number of channels | 8 |
Suitable field devices | |
| Field device | Solenoid Valve |
| Field device [2] | audible alarm |
| Field device [3] | visual alarm |
Connection | channel I: 1+, 2-, channel II: 3+, 4-, channel III: 5+, 6-, channel IV: 7+, 8-, channel V: 9+, 10-, channel VI: 11+, 12-, channel VII: 13+, 14-, channel VIII: 15+, 16- |
Current limit | 8 mA |
Open loop voltage | 20 V |
Line fault detection | can be switched on/off for each channel via configuration tool |
| Test current | 0.33 mA |
| Short-circuit | < 300 &Omega, |
| Open-circuit | > 50 k&Omega, |
Response time | 20 ms (depending on bus cycle time) |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication |
Indicators/settings |
LED indication | LED green: supply
LED red: line fault , communication error red flashing |
Coding | optional mechanical coding via front socket |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1 |
Conformity |
Electromagnetic compatibility | NE 21 |
Degree of protection | IEC 60529 |
Environmental test | EN 60068-2-14 |
Shock resistance | EN 60068-2-27 |
Vibration resistance | EN 60068-2-6 |
Damaging gas | EN 60068-2-42 |
Relative humidity | EN 60068-2-56 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 95 % non-condensing |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Vibration resistance | frequency range 10 ... 150 Hz, transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g, 10 cycles
frequency range 5 ... 100 Hz, transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g, 90 minutes at each resonance |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description |
Connection | removable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) |
Mass | approx. 750 g |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) |
Data for application in connection with hazardous areas |
EU-type examination certificate | PTB 97 ATEX 1074 U |
| Marking | II 2 G Ex d [ib] IIC Gb
II (2) D [Ex ib Db] IIIC |
Output | |
| Voltage | 28 V |
| Current | 13.5 mA |
| Power | 376 mW (characteristic curve rectangular type) |
Galvanic isolation | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2009
EN 60079-1:2007
EN 60079-11:2007
EN 60079-26:2007
EN 61241-11:2006 |
International approvals |
ATEX approval | PTB 97 ATEX 1075 , PTB 97 ATEX 1074 U
|
EAC approval | Russia: RU C-IT.MIII06.B.00129 |
Marine approval | |
| Lloyd Register | 15/20021 |
| DNV GL Marine | TAA0000034 |
| American Bureau of Shipping | T1450280/UN |
| Bureau Veritas Marine | 22449/B0 BV |
General information |
System information | The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate. |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |