General specifications |
Signal type | Analog input |
Supply |
Connection | SL1: 1a(-), 1b(-), 2a(+), 2b(+) |
Rated voltage | 20.4 ... 30 V DC bus powered via Termination Board |
Ripple | within the supply tolerance |
Current | &le, 95 mA at 20.4 V and &le, 63 mA at 30 V |
Power consumption | &le, 1.95 W |
Input |
Connection side | field side |
Connection | SL2: 5a(+), 1a(+), 1b(-), 5b(-), 7a(+), 3a(+), 3b(-), 7b(-) |
RTD | type Cu10, Cu50, Cu100, Pt10, Pt50, Pt100, Pt500, Pt1000, Ni100 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt50GOST, Pt1000GOST (P50353-92) |
| Measuring current | approx. 200 µ,A with RTD |
| Types of measuring | 2-, 3-, 4-wire connection |
| Lead resistance | max. 50 &Omega, per line |
| Measurement loop monitoring | sensor breakage, sensor short-circuit |
Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001) |
| Cold junction compensation | at field terminals |
| Measurement loop monitoring | sensor breakage |
Potentiometer | 0.1 ... 20 k&Omega, |
| Types of measuring | 3-wire connection |
Voltage | selectable within the range -100 ... 100 mV |
Input resistance | min. 1 M&Omega, (-100 ... 100 mV) |
Output |
Connection side | control side |
Connection | SL1: 8a(+), 7a(-), 10a(+), 9a(-) |
Output I, II | analog, current or voltage output |
| Current range | 0/4 ... 20 mA |
| Voltage range | 0 ... 5 V or 1 ... 5 V (on 250 &Omega,, 0.1 % internal shunt) |
| Fault signal | downscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43) |
| Source | load 0 ... 550 &Omega, , open-circuit voltage &le, 18 V |
| Sink | Voltage across terminals 7 ... 30 V. If the current is supplied from a source > 20 V,
series resistance of &ge, (V - 20)/0.0215 &Omega, is needed, where V is the source voltage.
The maximum value of the resistance is (V - 7)/0.0215 &Omega,. |
Fault indication output |
Connection | SL1: 6b |
Output type | open collector transistor (internal fault bus) |
Transfer characteristics |
Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP-switch |
Configuration | via DIP switches
via PACTware |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2006
For further information see system description. |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Mass | approx. 140 g |
Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
Mounting | on Termination Board |
Data for application in connection with hazardous areas |
EU-Type Examination Certificate | CESI 02 ATEX 086 |
| Marking | II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC , (-20 °C &le, Tamb &le, 60 °C) |
Certificate | PF 11 CERT 2109 X |
| Marking | II 3G Ex nA nC IIC T4 |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
CSA approval | |
| Control drawing | 366-017CS-12 (cCSAus) |
IECEx approval | IECEx TUN 04.0012 |
| Approved for | [Ex ia] IIC |