General specifications |
Signal type | Analog input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | Power Rail or terminals 9+, 10- |
Rated voltage | 19 ... 30 V DC |
Ripple | within the supply tolerance |
Rated current | < 20 mA |
Power consumption | 0.35 W (24 V and 1 mA sense current) |
Input |
Connection side | field side |
Connection | terminals 1, 2, 3, 4 |
Line fault detection | yes , at Pt100 |
Lead resistance | &le, 10 % of resistance value |
Transmission range | 0 ... 10 mA |
Available voltage | 9 V |
Line fault detection | 8 nA |
Output |
Connection side | control side |
Connection | terminals 5-, 7-, 6+, 8+ |
Current | 0 ... 10 mA |
Available voltage | 0 ... 4.2 V |
Fault signal | 400 &Omega,, depending on lead disconnected (measuring current &le, 1 mA)
> 400 &Omega,, terminal 3 lead disconnected in 2-/4-wire (measuring current &le, 0.3 mA) |
Transfer characteristics |
Accuracy | 0.1 % |
Deviation | 4-wire
Im &ge, 1 mA: ±0.1 % of Rm or ± 0.1 &Omega, (the larger value is applicable)
Im < 1 mA: accuracy reduces in proportion to Im.
e. g. Im = 0.1 mA: ± 1 % of Rm or 1 &Omega, (the larger value is applicable).
3-wire
Im &ge, 1 mA: (±0.1 % - 0.1 &Omega, Offset) or ± 0.2 &Omega, (the larger value is applicable)
Im < 1 mA: accuracy reduces in proportion to Im.
e. g. Im = 0.1 mA: (±1 % - 0.1 &Omega, Offset) or ± 1.1 &Omega, (the larger value is applicable) |
| Influence of ambient temperature | Im &ge, 1 mA, Rm &ge, 100 &Omega, : 0.01 %/K in the range -20 ... +60 °C (253 ... 333 K)
Im < 1 mA or Rm < 100 &Omega,: temperature stability reduces in proportion to Im or Rm |
Rise time | signal response time &le, 2 ms (10 ... 90 %)
response to application of Im: Rm > 50 &Omega, and Im < 5mA: <5msresponse to application of Im: Rm> 30 &Omega, and Im < 5mA: <10msresponse to application of Im: Rm> 18 &Omega, and Im < 5mA: < 20ms |
Galvanic isolation |
Input/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Input/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Indicators/settings |
Display elements | LED |
Control elements | DIP-switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2011 |
Degree of protection | IEC 60529:2001 |
Protection against electrical shock | UL 61010-1 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | BASEEFA 10 ATEX 0061 |
| Marking | II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I |
| Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
| Voltage | 12.4 V |
| Current | 17.4 mA |
| Power | 54 mW |
Supply | |
| Maximum safe voltage | 253 V (Attention! The rated voltage can be lower.) |
Output | |
| Maximum safe voltage | 253 V (Attention! The rated voltage can be lower.) |
Certificate | BASEEFA 10 ATEX 0062X |
| Marking | II 3G Ex ec IIC T4 Gc |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11:2012, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11:2012, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 |
International approvals |
FM approval | |
| Control drawing | 116-0129 (cFMus) |
UL approval | |
| Control drawing | 116-0332 (cULus) |
IECEx approval | IECEx BAS 10.0024
IECEx BAS 10.0025X |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I , Ex ec IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Accessories |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
- insertion bridge EBP 2- 5 |