Supply of spare parts for industrial enterprises around the world
Home Brands Pepperl+Fuchs 261918 KFD2-HLC-EX1.D.2W

Pepperl+Fuchs KFD2-HLC-EX1.D.2W 261918

Loop Converter KFD2-HLC-EX1.D.2W Pepperl+Fuchs 261918
Manufacturer
Pepperl+Fuchs
Name
KFD2-HLC-EX1.D.2W
Part number
261918
Country
Germany
Type
Loop Converter
Weight (g)
360
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


This isolated barrier is used for intrinsic safety applications. It is a HART loop converter that provides power to transmitters or can be connected to existing HART loops in parallel. It is able to evaluate up to four HART variables (PV, SV, TV, QV). Of those four HART variables, the data contained in any three of them can be converted to three different 4 mA ... 20 mA current signals. These loop signals can be connected to display devices or analog inputs on the process control system/ control system. In addition to the current outputs, two form C changeover relay contacts are available and can be programmed to operate at trip values from the HART variables. The unit is easily programmed by the use of a keypad located on the front of the unit or with the PACTware™ configuration software. For additional information, refer to the manual and www.pepperl-fuchs.com.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications KFD2-HLC-EX1.D.2W 261918

General specifications
Signal typeAnalog input
Supply
ConnectionPower Rail or terminals 23+, 24-
Rated voltage19 ... 30 V DC
Rated currentapprox. 130 mA at 24 V DC
Power dissipation2.5 W
Power consumption3.1 W
HART signal channels (intrinsically safe)
ConformityHART field device input (revision 5 to 7)
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
Connectionterminals 1, 2, 3, 4, 5, 6
Open circuit voltage/short-circuit currenttyp. 24 V / 28 mA
Input resistance250 &Omega, , 5 % (terminals 2, 3 and with jumper on 5, 6)
Available voltage&ge, 15.5 V at 20 mA, short-circuit protected
Output
Connection sidecontrol side
Connectionoutput I: terminals 10, 11, 12, output II: terminals 16, 17, 18 output III: terminals 7, 8, 9, output IV: terminals 13, 14, 15, output V: terminals 19, 20, 21
Output I, II
Output signalrelay and LED yellow
Mechanical life107 switching cycles
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Output III, IV, V
Output signalanalog
Current range4 ... 20 mA , (source or sink mode)
Loadmax. 650 &Omega, , source mode
Voltage range5 ... 30 V , sink mode from external supply
Fault signaldownscale I &le, 2 mA, upscale I &ge, 21.5 mA (acc. NAMUR NE43) or hold measurement value
Other outputsHART communicator on terminals 22, 24
Collective error messagePower Rail and LED red
Transfer characteristics
Output III, IV, V
Resolutionmax. 2 µ,A
Accuracy< 20 µ,A, 10 µ,A typ.
Influence of ambient temperature< ± 2 µ,A/K
Duration of measurement/Response delayHART message acquisition time plus 100 ms
Relayprogrammable either for fault or trip value (with direction, hysteresis and delay)
Galvanic isolation
Output I/IIfunctional insulation acc. to IEC 62103, rated insulation voltage 250 Veff
Output I, II/other circuitsreinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms
Output III/IV/V/power supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Indicators/settings
Display elementsLEDs , display
Control elementsControl panel
Configurationvia operating buttons via PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateBASEEFA 07 ATEX 0174
Marking II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC
Supply
Maximum safe voltage253 V AC (Attention! The rated voltage can be lower.)
Equipmentterminals 1, 4/3 (with link between terminals 4 and 5)
Voltage Uo25.2 V
Current Io104.9 mA
Power Po0.661 W
Equipmentterminals 2, 5/3
Voltage Ui< 28 V
Power Pi< 1.33 W
Voltage Uo1.1 V
Current Io11.9 mA
Power Po4 mW
Output I, IIterminals 10, 11, 12, 16, 17, 18 , non-intrinsically safe
Maximum safe voltage253 V (Attention! Um is no rated voltage.)
Contact loading253 V AC/1 A/cos &phi, > 0.7, 30 V DC/1 A resistive load (BASEEFA 07 ATEX 0174) 50 V AC/1 A/cos &phi, > 0.7, 30 V DC/1 A resistive load (Pepperl+Fuchs self-declaration)
Output III, IV, Vterminals 7, 8, 9, 13, 14, 15, 19, 20, 21 , non-intrinsically safe
Maximum safe voltage253 V (Attention! Um is no rated voltage.)
CertificatePF 07 CERT 1141 X
Marking II 3G Ex nA nC IIC T4 Gc
Galvanic isolation
Input/Other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0129
IECEx approval
IECEx certificateIECEx BAS 07.0047
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)