General specifications |
Signal type | Analog input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | terminals 14+, 15- or power feed module/Power Rail |
Rated voltage | 20 ... 30 V DC |
Ripple | within the supply tolerance |
Power dissipation/power consumption | &le, 0.64 W / 0.64 W |
Interface |
Programming interface | programming socket |
Input |
Connection side | field side |
Connection | terminals 1, 2, 3, 4 |
RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760) |
| Measuring current | approx. 200 µ,A with RTD |
| Types of measuring | 2-, 3-, 4-wire connection |
| Lead resistance | max. 50 &Omega, per line |
| Measurement loop monitoring | sensor breakage, sensor short-circuit |
Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001) |
| Cold junction compensation | external and internal |
| Measurement loop monitoring | sensor breakage |
Potentiometer | 0 ... 20 k&Omega, (2-wire connection), 0.8 ... 20 k&Omega, (3-wire connection) |
Voltage | selectable within the range -100 ... 100 mV |
Input resistance | &ge, 1 M&Omega, (-100 ... 100 mV) |
Output |
Connection side | control side |
Voltage output | 0 ... 5 V or 1 ... 5 V , output resistance: &le, 5 &Omega, , load: &ge, 10 k&Omega, |
Connection | terminals 7-, 8+ |
Fault signal | downscale 0 V or 0.5 V, upscale 5.375 V |
Transfer characteristics |
Deviation | |
| After calibration | Pt100: ± (0.06 % of measurement value in K + 0.1 K (4-wire connection))
thermocouple: ± (0.05 % of measurement value in °C + 1 K (1.2 K for types R and S))
this includes ± 0.8 K error of the cold junction compensation
mV: ± 50 µ,V
potentiometer: ± 0.05 % of full scale, (excludes errors due to lead resistance)
output: 1 to 5 V output: ± 4 mV from 0 to 103.1 % of span, 0 to 5 V output: ± 4 mV from 0.3 to 102.5 % of span |
| Influence of ambient temperature | deviation of CJC included:
Pt100: ± (0.0015 % of measurement value in K + 0.0075 % of span)/K &Delta,Tamb*)
thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.0075 % of span)/K &Delta,Tamb*)
mV: ± (0.01 % of measurement value + 0.0075 % of span)/K &Delta,Tamb*)
potentiometer: ± 0.0075 % of span/K &Delta,Tamb*)
*) &Delta,Tamb = ambient temperature change referenced to 23 °C (296 K) |
| Influence of supply voltage | < 0.01 % of span |
Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s |
Galvanic isolation |
Output/supply, programming input | functional insulation, rated insulation voltage 50 V AC
There is no electrical isolation between the programming input and the supply.
The programming cable provides galvanic isolation so that ground loops are avoided. |
Indicators/settings |
Display elements | LEDs |
Configuration | via PACTware |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Protection against electrical shock | UL 61010-1:2004 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 130 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-Type Examination Certificate | CESI 04 ATEX 143 |
| Marking | II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I |
| Input | Ex ia |
Inputs | terminals 1, 2, 3, 4 |
| Voltage Uo | 9 V |
| Current Io | 22 mA |
| Power Po | 50 mW |
Analog outputs, power supply, collective error | |
| Maximum safe voltage | 250 V (Attention! This is not the rated voltage.) |
Interface | |
| Maximum safe voltage | 250 V (Attention! The rated voltage is lower.), RS 232 |
Certificate | TÜV 02 ATEX 1797 X |
| Marking | II 3G Ex nA II T4 |
Galvanic isolation | |
| Input/Other circuits | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 |
International approvals |
UL approval | |
| Control drawing | 116-0410 |
CSA approval | |
| Control drawing | 116-0314 (cCSAus)
116-0347 |
IECEx approval | |
| IECEx certificate | IECEx TUN 07.0003
IECEx CML 16.0126X |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex nA IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Accessories |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
- FDT framework PACTware 4.1
- device type manager DTM Interface Technology
- adapter K-ADP-USB-AB |