Supply of spare parts for industrial enterprises around the world
Home Brands Pepperl+Fuchs 236165 HiDTB08-YC3-RRB-KS-CC-AI16

Pepperl+Fuchs HiDTB08-YC3-RRB-KS-CC-AI16 236165

Termination Board HiDTB08-YC3-RRB-KS-CC-AI16 Pepperl+Fuchs 236165
Manufacturer
Pepperl+Fuchs
Name
HiDTB08-YC3-RRB-KS-CC-AI16
Part number
236165
Country
Germany
Type
Termination Board
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


The function of the Termination Board as well as the connector pin assignment exactly fit the requirement of Yokogawa systems. Information about missing supply voltage of the interface modules is available for the system as potential-free contact. Wiring errors from field will be reported via the same relay contact if the interface module supports this function. The Termination Boards are supplied with a robust glass fiber reinforced plastic housing as standard. This design permits the fast and reliable installation on 35 mm DIN mounting rail acc. to EN 60715 in the cabinet.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications HiDTB08-YC3-RRB-KS-CC-AI16 236165

Supply
Nominal voltage24 V DC , in consideration of rated voltage of used isolators
Voltage drop0.9 V , voltage drop across the series diode on the termination board must be considered
Ripple&le, 10 %
Fusing2 A , in each case for 8 modules
Power dissipation&le, 500 mW , without modules
Reverse polarity protectionyes
Redundancy
SupplyRedundancy available. The supply for the isolators is decoupled, monitored and fused.
Fault indication output
Output typevolt-free contact
Contact loading30 V DC , 1 A
Indicators/settings
Display elementsLEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012 For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connection
Field sideexplosion hazardous area: spring terminals , blue
Control sidenon-explosion hazardous area: Yokogawa system connector, 40-pin
Supplypluggable screw terminals , black
Fault outputpluggable screw terminals , black
Core cross-sectionspring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2
Materialhousing: polycarbonate
Massapprox. 550 g
Dimensions205 x 175 x 153 mm (8.1 x 6.9 x 6.02 inch) , height including module assembly
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateCESI 11 ATEX 062
Marking II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Safe area
Maximum safe voltage250 V (Attention! Um is no rated voltage.)
Galvanic isolation
Field circuit/control circuitsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000
International approvals
IECEx approvalIECEx CES 11.0022
Approved for[Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I