General specifications |
Signal type | Digital Input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | Power Rail or terminals 9+, 10- |
Rated voltage | 19 ... 30 V DC |
Ripple | &le, 10 % |
Rated current | &le, 30 mA |
Power dissipation | &le, 600 mW |
Power consumption | &le, 600 mW |
Input |
Connection side | field side |
Connection | terminals 1+, 2-, 3+, 4- |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection | breakage I &le, 0.1 mA , short-circuit I &ge, 6.5 mA |
Pulse/Pause ratio | min. 20 ms / min. 20 ms |
Output |
Connection side | control side |
Connection | terminals 5, 6, 7, 8 |
Output I | signal , relay |
Output II | signal , relay |
Contact loading | 253 V AC/2 A/cos &phi, > 0.7, 126.5 V AC/4 A/cos &phi, > 0.7, 30 V DC/2 A resistive load |
Minimum switch current | 2 mA / 24 V DC |
Energized/De-energized delay | &le, 20 ms / &le, 20 ms |
Mechanical life | 107 switching cycles |
Transfer characteristics |
Switching frequency | &le, 10 Hz |
Galvanic isolation |
Input/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Input/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Output/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Input/input | Basic insulation according to EN 50178, rated insulation voltage 300 Veff |
Output/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP-switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Low voltage | |
| Directive 2014/35/EU | EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility | NE 21 |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | BASEEFA 06 ATEX 0092 |
| Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I |
| Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
| Voltage | 10.5 V |
| Current | 17.1 mA |
| Power | 45 mW (linear characteristic) |
Supply | |
| Maximum safe voltage | 253 V AC (Attention! Um is no rated voltage.) |
Output | |
| Contact loading | 253 V AC/2 A/cos &phi, > 0.7, 126.5 V AC/4 A/cos &phi, > 0.7, 30 V DC/2 A resistive load
|
| Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) |
Certificate | PF 06 CERT 0972 X |
| Marking | II 3G Ex nA nC IIC T4 Gc |
Output I, II | |
| Contact loading | 50 V AC/2 A/cos &phi, > 0.7, 30 V DC/2 A resistive load |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
FM approval | |
| Control drawing | 116-0419 (cFMus) |
UL approval | |
| Control drawing | 116-0420 (cULus) |
IECEx approval | IECEx BAS 06.0025 |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |