General specifications |
Signal type | Digital Input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | SL1: 1a(-), 1b(-), 2a(+), 2b(+) |
Rated voltage | 19 ... 30 V DC bus powered via Termination Board |
Ripple | &le, 10 % |
Rated current | &le, 30 mA |
Power dissipation | &le, 600 mW |
Power consumption | &le, 700 mW |
Input |
Connection side | field side |
Connection | SL2: 5a(+), 5b(-), 1a(+), 1b(-) |
Rated values | acc. to EN 60947-5-6 (NAMUR), see manual for electrical data |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection | breakage I &le, 0.1 mA , short-circuit I &ge, 6.5 mA |
Pulse/Pause ratio | min. 100 µ,s / min. 100 µ,s |
Output |
Connection side | control side |
Connection | SL1: 8a(+), 7a(-), 10a(+), 9a(-) |
Rated voltage | 30 V DC |
Rated current | 50 mA |
Response time | &le, 200 µ,s |
Signal level | 1-signal: (external voltage) - 1 V max. for 50 mA (Tamb = 25 °C (77 °F))
0-signal: blocked output (off-state current &le, 10 µ,A) |
Output I | signal , Transistor |
Output II | signal , Transistor |
Fault indication output |
Connection | SL1: 6b |
Output type | open collector transistor (internal fault bus) |
Transfer characteristics |
Switching frequency | &le, 5 kHz |
Galvanic isolation |
Output/power supply | basic insulation acc. to EN 50178, rated insulation voltage of 50 V AC |
Output/Output | basic insulation acc. to EN 50178, rated insulation voltage of 50 V AC |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP-switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Galvanic isolation | EN 50178:1997 |
Electromagnetic compatibility | NE 21:2006
For further information see system description. |
Degree of protection | IEC 60529 |
Protection against electrical shock | IEC 61140 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Relative humidity | &le, 90 % , non-condensing |
Mechanical specifications |
Degree of protection | IP20 |
Mass | approx. 100 g |
Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
Mounting | on Termination Board |
Coding | pin 1 and 2 trimmed
For further information see system description. |
Data for application in connection with hazardous areas |
EU-type examination certificate | BVS 09 ATEX E 157 |
| Marking | II (1)GD [Ex ia] IIC, [Ex iaD] [circuit(s) in zone 0/1/2/20/21/22]
I (M1) [Ex ia] I |
| Input | Ex ia, Ex iaD |
| Voltage | 10.5 V |
| Current | 17.1 mA |
| Power | 45 mW (linear characteristic) |
Supply | |
| Maximum safe voltage | 253 V AC (Attention! Um is no rated voltage.) |
Output | |
| Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 |
International approvals |
UL approval | |
| Control drawing | 116-0331 |
IECEx approval | IECEx BVS 09.0060 |
| Approved for | [Ex ia Ga] IIC, [Ex ia] I , [Ex iaD] |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |