Supply of spare parts for industrial enterprises around the world

Pepperl+Fuchs HIC2842 214234

Switch Amplifier HIC2842 Pepperl+Fuchs 214234
Manufacturer
Pepperl+Fuchs
Name
HIC2842
Part number
214234
Country
Germany
Type
Switch Amplifier
Weight (g)
139
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. The proximity sensor or switch controls two passive transistors for the safe area load. Both transistor outputs are isolated from each other and isolated from the power supply. The mode of operation can be reversed using switches S1 and S3. Switches S2 and S4 enable or disable line fault detection of the field circuit. During an error condition, the transistors revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44. A separate output bus is available. The fault conditions can be monitored via a Fault Indication Board. This module mounts on a HiC Termination Board.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications HIC2842 214234

General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionSL1: 1a(-), 1b(-), 2a(+), 2b(+)
Rated voltage19 ... 30 V DC bus powered via Termination Board
Ripple&le, 10 %
Rated current&le, 30 mA
Power dissipation&le, 600 mW
Power consumption&le, 700 mW
Input
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-), 1a(+), 1b(-)
Rated valuesacc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Open circuit voltage/short-circuit currentapprox. 10 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I &le, 0.1 mA , short-circuit I &ge, 6.5 mA
Pulse/Pause ratiomin. 100 µ,s / min. 100 µ,s
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-), 10a(+), 9a(-)
Rated voltage30 V DC
Rated current50 mA
Response time&le, 200 µ,s
Signal level1-signal: (external voltage) - 1 V max. for 50 mA (Tamb = 25 °C (77 °F)) 0-signal: blocked output (off-state current &le, 10 µ,A)
Output Isignal , Transistor
Output IIsignal , Transistor
Fault indication output
ConnectionSL1: 6b
Output typeopen collector transistor (internal fault bus)
Transfer characteristics
Switching frequency&le, 5 kHz
Galvanic isolation
Output/power supplybasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Output/Outputbasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Indicators/settings
Display elementsLEDs
Control elementsDIP-switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Galvanic isolationEN 50178:1997
Electromagnetic compatibilityNE 21:2006 For further information see system description.
Degree of protectionIEC 60529
Protection against electrical shockIEC 61140
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Relative humidity&le, 90 % , non-condensing
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Mountingon Termination Board
Codingpin 1 and 2 trimmed For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateBVS 09 ATEX E 157
Marking II (1)GD [Ex ia] IIC, [Ex iaD] [circuit(s) in zone 0/1/2/20/21/22] I (M1) [Ex ia] I
InputEx ia, Ex iaD
Voltage10.5 V
Current17.1 mA
Power45 mW (linear characteristic)
Supply
Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
Output
Maximum safe voltage253 V AC (Attention! The rated voltage can be lower.)
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000
International approvals
UL approval
Control drawing116-0331
IECEx approvalIECEx BVS 09.0060
Approved for[Ex ia Ga] IIC, [Ex ia] I , [Ex iaD]
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.