General specifications |
Switching function | Normally open (NO) |
Output type | Two-wire |
Rated operating distance | 5 mm |
Installation | flush |
Output polarity | DC |
Assured operating distance | 0 ... 4.05 mm |
Actual operating distance | 4.5 ... 5.5 mm typ. 5 mm |
Reduction factor rAl | 0.37 |
Reduction factor rCu | 0.33 |
Reduction factor r304 | 0.7 |
Output type | 2-wire |
Nominal ratings |
Operating voltage | 5 ... 60 V |
Switching frequency | 0 ... 350 Hz |
Hysteresis | 1 ... 10 typ. 5 % |
Reverse polarity protection | reverse polarity tolerant |
Short-circuit protection | pulsing |
Voltage drop | &le, 5 V |
Operating current | 2 ... 100 mA |
Lowest operating current | 2 mA |
Off-state current | 0 ... 0.5 mA typ. |
Switching state indicator | all direction LED, yellow |
Functional safety related parameters |
MTTFd | 1739 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives |
Standard conformity | |
| Standards | EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012 |
Approvals and certificates |
UL approval | cULus Listed, General Purpose |
CSA approval | cCSAus Listed, General Purpose |
CCC approval | Certified by China Compulsory Certification (CCC) |
Ambient conditions |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Mechanical specifications |
Connection type | cable PVC , 2 m |
Cable version | PA |
Core cross-section | 0.34 mm2 |
Housing material | Stainless steel 1.4305 / AISI 303 |
Sensing face | PBT |
Degree of protection | IP66 / IP67 |
Cable | |
| Cable diameter | 4.8 mm ± 0.2 mm |
| Bending radius | > 10 x cable diameter |
Equipment protection level Gc (nA) |
Certificate | PF 15CERT3754 X |
CE marking | [*PD-Z02586A*] |
ATEX marking | II 3G Ex nA IIC T6 Gc
The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013, EN 60079-15:2010
Ignition protection category n
Use is restricted to the following stated conditions |
Special conditions | |
| Maximum operating current IL | The maximum permissible load current must be restricted to the values given in the following list. High load currents and load short-circuits are not permitted. |
| Maximum operating voltage UBmax | The maximum permissible operating voltage UB max is restricted to the values in the following list. Tolerances are not permissible. |
| Maximum permissible ambient temperature TUmax | dependant of the load current IL and the max. operating voltage UBmax
Information can be taken from the following list. |
| at UBmax=60 V, IL=100 mA | 50 °C (122 °F) |
| at UBmax=60 V, IL=50 mA | 56 °C (132.8 °F) |
| at UBmax=60 V, IL=25 mA | 60 °C (140 °F) |
Equipment protection level Dc (tc) |
CE marking | [*PD-Z02586A*] |
ATEX marking | II 3D Ex tc IIIC T80°C Dc
The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013, EN 60079-31:2014
Protection by enclosure tc Some of the information in this instruction manual is more specific than the information provided in the datasheet. |
General | The corresponding datasheets, declarations of conformity, EC-type examination certificates, certifications, and control drawings, where applicable (see datasheets), form an integral part of this document. These documents can be found at www.pepperl-fuchs.com. The maximum surface temperature of the device was determined without a layer of dust on the apparatus. Some of the information in this instruction manual is more specific than the information provided in the datasheet. |
Special conditions | |
| Maximum permissible ambient temperature TUmax | dependant of the load current IL and the max. operating voltage UBmax
Information can be taken from the following list. |
| at UBmax=60 V, IL=100 mA | 50 °C (122 °F) |
| at UBmax=60 V, IL=50 mA | 56 °C (132.8 °F) |
| at UBmax=60 V, IL=25 mA | 60 °C (140 °F) |
Equipment protection level Dc (tD) |
General | The apparatus has to be operated according to the appropriate data in the data sheet and in this instruction manual.
The maximum surface temperature has been determined in accordance with method A without a dust layer on the equipment.
The data stated in the data sheet are restricted by this operating instruction!
The special conditions must be adhered to! |
Special conditions | |
| Maximum permissible ambient temperature TUmax | dependant of the load current IL and the max. operating voltage UBmax
Information can be taken from the following list. |
| at UBmax=60 V, IL=100 mA | 50 °C (122 °F) |
| at UBmax=60 V, IL=50 mA | 56 °C (132.8 °F) |
| at UBmax=60 V, IL=25 mA | 60 °C (140 °F) |
General information |
Use in the hazardous area | see instruction manuals |
| Category | 3G, 3D |