General specifications |
Signal type | Digital Input |
Functional safety related parameters |
MTTFd | 100 a |
Supply |
Rated voltage | 200 ... 230 V AC , 100 &hellip, 130 V AC, 50/60 Hz
20 VDC ... 30 VDC |
Fusing | external fusing 4 A |
Power consumption | AC: < 5 VA
DC: < 5 W |
Input |
Connection side | field side |
Input 1 |
Connection | terminals 8-, 9+ |
Connectable sensor types | NAMUR sensors according to DIN EN 60947-5-6 |
Open loop voltage | 8.2 V DC |
Short-circuit current | 6.5 mA |
Switching point | 1.2 ... 2.1 mA Switching hysteresis approx. 0.2 mA |
Input frequency | 0.002 ... 10000 Hz, pulse length/duration: &ge, 20µ,s |
Impedance | 1.2 k&Omega, |
Input 2 |
Switching point | high: 16 ... 30 V DC, max.10 mA due to integrated constant current sink, Ri &cong, 3 k&Omega,
low: 0 ... 6 V DC |
Input frequency | 0.002 ... 40000 Hz, pulse length/duration: &ge, 12µ,s |
Connection | terminals 7+, 13- sensor supply
terminals 14, 15 NPN/PNP input (galvanically isolated) |
Connectable sensor types | Two, three, or four-wire proximity switch, incremental rotary encoder, or externally generated pulses 16 ... 30 V |
Sensor supply | 19 ... 28 V DC non-stabilised, &le, 30 mA short-circuit protected |
Input 3 |
Start-up override | Triggering by external signal 16 ... 30 V or Place jumper between terminals 2/3 or by switching on supply voltage (terminal 2 and terminal 3 permanently bridged) |
Jumpering time | 0.1 ... 999.9 s (External trigger signal) |
Output |
Connection side | control side |
Relay | 1 changeover contact
NO, NC, COM |
Sensor supply | 24 V DC ± 10 %, 30 mA , short-circuit protected |
Contact loading | 250 V AC/2 A/ cos &phi, &ge, 0.7
40 V DC/2 A |
Delay | &le, 20 ms (incl. calculation time) |
Mechanical life | &ge, 30.000.000 switching cycles |
Transfer characteristics |
Changing interval | 5 ms (Internal processing time) |
Time delay before availability | &le, 400 ms |
Measuring error | 0 ... 40000 Hz: &le, ±0,10%
Display: ±1 digit |
Timer function | ON-delay, OFF-delay, one shot, pulse extension |
Time | 0 ... 999.9 s , mode of operation reversible |
Indicators/settings |
Display elements | display , 4-digit, 7-segment red display, 7 mm digit height and LED |
LED indication | yellow LED : switching state |
Display indication | 0.002 ... 9999 Hz or
0,01 ... 9999 min-1 |
Control elements | Control panel |
Configuration | via operating buttons |
Labeling | space for labeling at the front |
Standard conformity |
Electromagnetic compatibility | acc. to EN 50081-2 / EN 50082-2 |
Ambient conditions |
Ambient temperature | -25 ... 40 °C (-13 ... 104 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Relative humidity | max. 80 %, not condensing |
Altitude | 0 ... 2000 m |
Operating conditions | The device has only to be used in an indoor area. |
Mechanical specifications |
Connection assembly | Caution: Please be aware that the device may only be connected to a switchable power supply. The switch or circuit breaker must be easy to reach and identified as the separator for the device. |
Degree of protection | IP20 |
Connection | coded, removable terminals , max. core cross section 0.34 ... 2.5 mm2 |
Construction type | modular terminal housing in Makrolon, System KF
For use in the switch cabinet/switch cabinet module |
Mounting | snap-on to 35 mm standard rail or screw fixing |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |