Supply of spare parts for industrial enterprises around the world
Home Brands Pepperl+Fuchs 188848 VAA-4E4A-G2-ZA/EA2

Pepperl+Fuchs VAA-4E4A-G2-ZA/EA2 188848

Module VAA-4E4A-G2-ZA/EA2 Pepperl+Fuchs 188848
Manufacturer
Pepperl+Fuchs
Name
VAA-4E4A-G2-ZA/EA2
Part number
188848
Country
Germany
Type
Module
Weight (g)
185
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


The VAA-4E4A-G2-ZA/EA2 is an AS-Interface module with 4 Inputs and 4 outputs. Mechanical contacts (e. g. push buttons) as well as 2-, 3- and 4-wire sensors can be connected to the inputs. The outputs are electronic outputs, which can be collectively loaded with 24 V DC and 1 A per output. The IP67 flat module is ideal for applications in the field. An addressing jack is integrated in the module. The connection for the sensors/actuators is via M12 x 1 screw connections. An LED is provided on the top of the module, for each channel, to indicate the current switching status. Similarly, an LED is provided to monitor the AS-Interface communication and to indicate that the module has the address 0. LEDs are also provided to indicate AS-Interface voltage and external power supply. The mounting plate U-G2FF is used as standard for the connection to the AS-Interface flat cable and the external 24 V DC supply. The specially designed base enables the user to connect flat cable from both sides. The device incorporates communication monitoring, which switches off power to the outputs if no communication has taken place on the AS-Interface line for longer than 40 ms. An overloading of the internal input supply or of the outputs is signalled to the AS-interface master via the Peripheral fault function. Communication via the AS-Interface remains intact. Note: The mounting base for the module is sold separately.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications VAA-4E4A-G2-ZA/EA2 188848

Product Description
G2 flat module 4 inputs (PNP) and 4 electronic outputs
General specifications
Slave typeStandard slave
AS-Interface specificationV3.0
Required master specification&ge, V2.0
UL File NumberE223772
Functional safety related parameters
MTTFd140 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Indicators/operating means
LED FAULTerror display, LED red red: communication error or address is 0 red flashing: overload of sensor power supply or outputs
LED PWRAS-Interface voltage, LED green
LED AUXext. auxiliary voltage UAUX , LED green
LED INswitching state (input), 4 LED yellow
LED OUTSwitching state (output), 4 LED yellow
Electrical specifications
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current&le, 40 mA (without sensors) / max. 220 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC
Supplyfrom AS-Interface
Voltage21 ... 31 V
Current loading capacity&le, 180 mA (TB &le, 40 °C), &le, 140 mA (TB &le, 60 °C), , overload and short-circuit protected
Input current&le, 9 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)&le, 3 mA
1 (attenuated)&ge, 5 mA
Signal delay< 2 ms (input/AS-Interface)
Signal frequency&le, 250 Hz
Output
Number/Type4 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Current2 A per output Sum 4 A (TB &le, 40 °C) Sum 3 A (TB &le, 60 °C)
Voltage&ge, (UAUX - 0.5 V)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
InputEN 61131-2:2007
Emitted interferenceEN 61000-6-4:2001
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2001
Programming instructions
ProfileS-7.F
IO code7
ID codeF
ID1 codeF
ID2 codeE
Data bits (function via AS-Interface) input output
D0 IN1 OUT1
D1 IN2 OUT2
D2 IN3 OUT3
D3 IN4 OUT4
Parameter bits (programmable via AS-i)function
P0communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
P1not used
P2not used
P3not used
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude&le, 2000 m above MSL
Pollution degree3
Mechanical specifications
Degree of protectionIP67
ConnectionCable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector
Material
HousingPBT
Mass150 g
Tightening torque, cable gland0.4 Nm
MountingMounting plate