Supply of spare parts for industrial enterprises around the world
Home Brands Pepperl+Fuchs 132965 KFD2-SR2-2.W.SM

Pepperl+Fuchs KFD2-SR2-2.W.SM 132965

Frequency Converter KFD2-SR2-2.W.SM Pepperl+Fuchs 132965
Manufacturer
Pepperl+Fuchs
Name
KFD2-SR2-2.W.SM
Part number
132965
Country
Germany
Type
Frequency Converter
Weight (g)
166
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


This signal conditioner provides the galvanic isolation between field circuits and control circuits. This device is a standstill monitor that accepts input frequency pulses and triggers an output when the frequency drops below a preselected limit value. Two start-up override values are available. This unit can also be used to determine rotation direction. During an error condition or a power loss, the relay reverts to its de-energized state and the LEDs indicate the fault according to NAMUR NE 44. A line fault is not indicated. The device has LED status indicators for direction of rotation detection, limit detection, supply, and hardware faults. The device is easily configured by the use of DIP switches. For additional information, refer to www.pepperl-fuchs.com.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications KFD2-SR2-2.W.SM 132965

General specifications
Signal typeDigital Input
Programmingvia DIP switch and programmable
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Connectionterminals 14+, 15-
Rated voltage20 ... 30 V DC
Power consumptionmax. 1.5 W
Input
Connection sidefield side
ConnectionInput I: terminals 1+, 2+, 3- , Input II: terminals 4+, 5+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionnot available
Control inputsensor power supply approx. 8.2 V, impedance 1.2 k&Omega,
Pulse duration> 200 µ,s for standstill monitoring, > 250 µ,s for rotation direction detecion
Output
Connection sidecontrol side
Connectionoutput I: terminals 7, 8, 9 , output II: terminals 10, 11, 12
Contact loading253 V AC/2 A/cos &phi, > 0.7, 126.5 V AC/4 A/cos &phi, > 0.7, 40 V DC/2 A resistive load
Minimum switch current2 mA / 24 V DC
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Mechanical life107 switching cycles
Trip valuefor standstill monitoring: 0.1 Hz, 0.5 Hz, 2 Hz, 10 Hz adjustable via DIP switch (S1 and S2)
Transfer characteristics
Accuracy5 % (S3 = I), 30 % (S3 = II)
Start-up override5 seconds or 20 seconds, programmable
Frequency range&le, 2 kHz
Rotation direction detection90° phase difference between pulse input signal 1 and 2, overlapping &ge, 125 µ,s
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP-switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
InputEN 60947-5-6:2000
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03)