Switch Amplifier KFA6-ER-EX1.W.LB Pepperl+Fuchs 115163
Manufacturer
Pepperl+Fuchs
Name
KFA6-ER-EX1.W.LB
Part number
115163
Country
Germany
Type
Switch Amplifier
Weight (g)
179
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


This isolated barrier is used for intrinsic safety applications. It provides the AC measuring voltage for the level sensing electrodes. Once the measured medium reaches the electrodes, the unit reacts by energizing a form C changeover relay contact. The module is voltage and temperature stabilized and guarantees a defined switching characteristic. It can be used for on/off control or minimum/maximum control. A signal delay feature is available and is adjustable between 0.5 s and 10 s. This module can also monitor the field circuit for lead breakage (LB). LB is indicated by a red LED. If LB monitoring is selected, output II serves as the fault signal output, otherwise, it will follow the function of output I.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications KFA6-ER-EX1.W.LB 115163

Product Description
230 V AC
General specifications
Signal typeDigital Input
Supply
Connectionterminals 14, 15
Rated voltage207 ... 253 V AC, 45 ... 65 Hz
Rated current&le, 7 mA
Power consumption< 1.2 W
Input
Connection sidefield side
Connectionterminals 1 (mass), 2 (min), 3 (max)
Control inputmin./max. control system: terminals 1, 2, 3 on/off control system: terminals 1, 3
Response sensitivity1 ... 150 k&Omega, , adjustable via potentiometer
Output
Connection sidecontrol side
Connectionterminals 7, 8, 9, 10, 11, 12
Switching powermax. 192 W , 2000 VA
Outputsignal , relay
Contact loading253 V AC/2 A/cos &phi, > 0.7, 40 V DC/2 A resistive load
Time constant for signal damping0.5 s, 2 s, 5 s, 10 s
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP-switch potentiometer
Configurationvia DIP switches via potentiometer
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals , max. 2.5 mm2
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateDMT 00 ATEX E 032
Marking II (1)G [EEx ia] IIC [circuit(s) in zone 0/1/2]
Input[EEx ia] IIC
Voltage10 V
Current2.5 mA
Power6 mW
Supply
Maximum safe voltage265 V AC (Attention! Um is no rated voltage.)
Output
Contact loading253 V AC/2 A/cos &phi, > 0.7, 40 V DC/2 A resistive load
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013, EN 60079-11:2012
General information