General specifications |
Switching function | Normally closed (NC) |
Output type | NAMUR |
Rated operating distance | 6 mm |
Installation | flush |
Assured operating distance | 0 ... 4.86 mm |
Reduction factor rAl | 0.4 |
Reduction factor rCu | 0.3 |
Reduction factor r304 | 0.85 |
Output type | 2-wire |
Nominal ratings |
Nominal voltage | 8.2 V (Ri approx. 1 k&Omega,) |
Switching frequency | 0 ... 2000 Hz |
Hysteresis | typ. % |
Current consumption | |
| Measuring plate not detected | min. 3 mA |
| Measuring plate detected | &le, 1 mA |
Functional safety related parameters |
MTTFd | 4566 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives |
Standard conformity | |
| NAMUR | EN 60947-5-6:2000
IEC 60947-5-6:1999 |
| Standards | EN 60947-5-2:2007
IEC 60947-5-2:2007 |
Approvals and certificates |
UL approval | cULus Listed, General Purpose |
CSA approval | cCSAus Listed, General Purpose |
CCC approval | CCC approval / marking not required for products rated &le,36 V |
Ambient conditions |
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
Mechanical specifications |
Connection type | cable PVC , 2 m |
Core cross-section | 0.75 mm2 |
Housing material | Stainless steel 1.4305 / AISI 303 |
Sensing face | PBT |
Degree of protection | IP68 |
Cable | |
| Bending radius | > 10 x cable diameter |
Equipment protection level Gb |
CE marking | [*PD-Z02585A*] |
ATEX marking | II 2G Ex ia IIC T6&hellip,T1 Gb
The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection Intrinsic safety
Use is restricted to the following stated conditions |
Appropriate type | NJ 6-22-N... |
Effective internal capacitance | max. 130 nF , a cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H , a cable length of 10 m is considered. |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. |
Equipment protection level Gc (ic) |
Certificate | PF 13 CERT 2895 X |
CE marking | [*PD-Z02586A*] |
ATEX marking | II 3G Ex ic IIC T6&hellip,T1 Gc
The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection category ic
Use is restricted to the following stated conditions |
Effective internal capacitance | max. 130 nF , a cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H , A cable length of 10 m is considered.
|
Special conditions | |
| for Pi=34 mW, Ii=25 mA, T6 | 55 °C (131 °F) |
| for Pi=34 mW, Ii=25 mA, T5 | 55 °C (131 °F) |
| for Pi=34 mW, Ii=25 mA, T4-T1 | 55 °C (131 °F) |
| for Pi=64 mW, Ii=25 mA, T6 | 55 °C (131 °F) |
| for Pi=64 mW, Ii=25 mA, T5 | 55 °C (131 °F) |
| for Pi=64 mW, Ii=25 mA, T4-T1 | 55 °C (131 °F) |
| for Pi=169 mW, Ii=52 mA, T6 | 41 °C (105.8 °F) |
| for Pi=169 mW, Ii=52 mA, T5 | 41 °C (105.8 °F) |
| for Pi=169 mW, Ii=52 mA, T4-T1 | 41 °C (105.8 °F) |
| for Pi=242 mW, Ii=76 mA, T6 | 29 °C (84.2 °F) |
| for Pi=242 mW, Ii=76 mA, T5 | 29 °C (84.2 °F) |
| for Pi=242 mW, Ii=76 mA, T4-T1 | 29 °C (84.2 °F) |
Equipment protection level Da |
CE marking | [*PD-Z02585A*] |
ATEX marking | II 1D Ex ia IIIC T135°C Da
The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013, EN 60079-11:2012
Ignition protection Intrinsic safety
Use is restricted to the following stated conditions |
Appropriate type | NJ 6-22-N... |
Effective internal capacitance | max. 130 µ,F
A cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H
A cable length of 10 m is considered. |
Equipment protection level Dc (tc) |
CE marking | [*PD-Z02586A*] |
ATEX marking | II 3D Ex tc IIIC T80°C Dc
The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013, EN 60079-31:2014
Protection by enclosure tc Some of the information in this instruction manual is more specific than the information provided in the datasheet. |
General | The corresponding datasheets, declarations of conformity, EU type examination certificates, certificates, and control drawings, where applicable (see datasheets), form an integral part of this document. These documents are available at www.pepperl-fuchs.com. The maximum surface temperature of the device was determined without a layer of dust on the apparatus. Some of the information in this instruction manual is more specific than the information provided in the datasheet. |
Special conditions | |
| Maximum permissible ambient temperature TUmax | Values can be obtained from the following list, depending on the max. operating voltage Ub max and the minimum series resistance Rv. |
| at UBmax=9 V, RV=562 &Omega, | 58 °C (136.4 °F) |
| using an amplifier in accordance with EN 60947-5-6 | 58 °C (136.4 °F) |
General information |
Use in the hazardous area | see instruction manuals |
| Category | 2G, 3G, 3D |