Supply of spare parts for industrial enterprises around the world
Home Brands Pepperl+Fuchs 106342 NJ1,5-18GM-N-D

Pepperl+Fuchs NJ1,5-18GM-N-D 106342

Inductive sensor NJ1,5-18GM-N-D Pepperl+Fuchs 106342
Manufacturer
Pepperl+Fuchs
Name
NJ1,5-18GM-N-D
Part number
106342
Country
Germany
Type
Inductive sensor
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


Order Pepperl+Fuchs 106342 Spare Parts Online for Enhanced Efficiency

For industries seeking reliable components, Pepperl+Fuchs 106342 Industrial parts are the ideal choice. Built with precision and innovation, these Pepperl+Fuchs 106342 spare parts optimize industrial operations across USA.

What Makes 2technologie Stand Out?

  • Comprehensive Options: A full range of Pepperl+Fuchs 106342 spares for all applications.

  • Swift Delivery: Quick access to Pepperl+Fuchs 106342 spare parts near me or online.

  • Cost-Effective Solutions: Quality Pepperl+Fuchs 106342 Industrial products at the best prices.

  • Proven Expertise: A trusted provider of Pepperl+Fuchs 106342 Industrial components.

Order Pepperl+Fuchs 106342 spare parts today and experience the 2technologie difference!

Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications NJ1,5-18GM-N-D 106342

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance1.5 mm
Installationflush
Assured operating distance0 ... 1.22 mm
Reduction factor rAl 0
Reduction factor rCu 0
Reduction factor r304 0.55
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 k&Omega,)
Switching frequency0 ... 400 Hz
Hysteresistyp. %
Current consumption
Measuring plate not detectedmin. 3 mA
Measuring plate detected&le, 1 mA
Limit data
Operating pressure350 bar (5076.4 psi)
Functional safety related parameters
MTTFd10880 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Approvals and certificates
EAC conformityTR CU 012/2011
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
Ambient conditions
Ambient temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Connection typecable PVC , 2 m
Core cross-section0.34 mm2
Housing materialStainless steel 1.4305 / AISI 303
Sensing faceCeramic
Degree of protectionIP66 / IP68
Cable
Cable diameter4.8 mm ± 0.2 mm
Bending radius> 10 x cable diameter
Equipment protection level Gb
CE marking[*PD-Z02585A*]
ATEX marking II 2G Ex ia IIC T6&hellip,T1 Gb The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ1,5-18GM-N-D..
Effective internal capacitancemax. 50 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 60 µ,H , a cable length of 10 m is considered.
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Equipment protection level Da
CE marking[*PD-Z02585A*]
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ1,5-18GM-N-D..
Effective internal capacitancemax. 50 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 60 µ,H , a cable length of 10 m is considered.
Maximum permissible ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained.
General information
Use in the hazardous areasee instruction manuals
Category2G, 1D