Pepperl+Fuchs K-LB-1.30 098908

Module K-LB-1.30 Pepperl+Fuchs 098908
Manufacturer
Pepperl+Fuchs
Name
K-LB-1.30
Part number
098908
Country
Germany
Type
Module
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


The device limits induced transients of different causes, e. g. lightning or switching operations. The limitation is achieved by diverting the current to earth and limiting the signal loop voltage during the duration of the overvoltage pulse. The device is HART transparent. The device is mounted on a 35 mm DIN mounting rail according to EN 60715. Note: Always connect the device to high-quality ground connections. The device must have the same potential as the devices it protects. Install the ground system in accordance with the applicable regulations.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications K-LB-1.30 098908

Product Description
2-line protection
General specifications
Number of protected signal lines2
Topologynon-grounded
Electrical specifications
Connectionprotected area: terminals 7, 8 unprotected area: terminals 1, 2
Rated current250 mA
Leakage current< 5 µ,A at 24 V and 25 °C (77 °F) , line-line
Nominal voltage24 V DC
Maximum continuous operating voltage30 V DC
Series resistance< 0.5 &Omega, per line
Impulse rating10 kV/5 kA (category C2) 2 kV/2 kA (category D1)
Impulse discharge current (10/350 µ,s)2 kA per line (2x)
Nominal discharge current (8/20 µ,s)5 kA per line (10x)
Rated surge current (8/20 µ,s)10 kA per line (1x)
Total discharge current (8/20 µ,s)20 kA (1x)
Voltage protection levelmax. 75 V line-line for nominal discharge current In max. 1.2 kV line-earth for nominal discharge current In
Impulse reset time< 30 ms
Insertion loss&le, 0.05 dB, at 0 ... 4 kHz, in 600 &Omega,-System &le, 3 dB, at 0 ... 174 kHz, in 100 &Omega,-System
Indicators/settings
Labelingspace for labeling at the front
Conformity
Degree of protectionIEC 60529:2013
Surge protective devices for low voltageEN 61643-21:2001+A1:2009+A2:2013 IEC 61643-21:2001+A1:2008+A2:2012
Operating conditions
Installation conditions
Mounting locationindoor
Ambient conditions
Ambient temperature-30 ... 80 °C (-22 ... 176 °F) For usage in hazardous area observe EC-type examination certificate.
Relative humidity5 ... 95 %
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Core cross-section2 x 2.5 mm2
Massapprox. 100 g
Dimensions12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch)
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificatePTB 00 ATEX 2176 X
Marking II 2(1)G Ex ia IIC T6/T5/T4
Temperature classT6 for ambient temperature &le, 50 °C T5 for ambient temperature &le, 70 °C T4 for ambient temperature &le, 80 °C
Voltage30 V
Current250 mA
Internal capacitancenegligible
Internal inductance200 µ,H
CertificatePF 16 CERT 4065 X
Marking II (3)D [Ex ic Dc] IIIC
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012
International approvals
CSA approval
Control drawing116-0187 (cCSAus)
IECEx approval
IECEx certificateIECEx BAS 14.0010X
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.