General specifications |
Signal type | Analog input |
Supply |
Rated voltage | 12 ... 35 V DC loop powered |
Power dissipation | 0.4 W |
Input |
Connection side | field side |
Connection | terminals 1+, 2-, 3- thermocouple E, J, K, N, R, S or T, cold junction referenced to 0 °C (32 °F) |
Lead resistance | max. 100 &Omega, per line |
Current | lead monitoring ON: &le, 15 nA, OFF: &le, 1 nA |
Output |
Connection side | control side |
Connection | terminals 9+, 8- |
Load | (U -12 V) / 0.02 A |
Current output | 4 ... 20 mA , limited to &le, 35 mA |
Fault signal | downscaling &le, 3 mA , upscaling &ge, 22 mA |
Transfer characteristics |
Measurement range | span 4 ... 100 mV, zero point -12 ... 60 mV , both adjustable |
Deviation | |
| After calibration | 0.1 % of full-scale value ± 1 K for the cold junction |
| Temperature effect | temperature deviation 0.015 % of the span/K or 1.5 µ,V/K cold junction ± 2 K (calibrated at Tamb = 20 °C (68 °F)) |
| Influence of supply voltage | 6.5 ppm/V |
Characteristic curve | the output voltage is linearly proportionate to the input voltage (not to temperature) |
Rise time | 250 ms |
Galvanic isolation |
Input/Output | safe isolation according to EN 50178, rated insulation voltage 253 Veff |
Indicators/settings |
Control elements | DIP-switch
rotary switch |
Configuration | via DIP switches
via rotary switch |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Insulation coordination | EN 50178 |
Galvanic isolation | EN 50178 |
Degree of protection | IEC 60529 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-Type Examination Certificate | ZELM 00 ATEX 0035 |
| Marking | II (1)GD [EEx ia] IIC |
| Voltage | 16.1 V |
| Current | 0.8 mA |
| Power | 3.2 mW |
Output | |
| Maximum safe voltage | 60 V (Attention! The rated voltage can be lower.) |
Certificate | TÜV 01 ATEX 1777 X |
| Marking | II 3G Ex nA II T4 |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
CSA approval | |
| Control drawing | 116-0132 |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |