Supply of spare parts for industrial enterprises around the world

Pepperl+Fuchs KFD0-TR-1 038307

Signal Converter KFD0-TR-1 Pepperl+Fuchs 038307
Manufacturer
Pepperl+Fuchs
Name
KFD0-TR-1
Part number
038307
Country
Germany
Type
Signal Converter
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


This isolated signal conditioner is a loop-powered isolator that converts the resistance from a 3-wire RTD to a 4 mA ... 20mA signal and provides isolation for non-intrinsically safe applications. A selectable analog linearization ensures a temperature linear 4 mA ... 20mA output between 25 °C ... 375 °C. It also features conveniently located DIP switches and potentiometers to make field calibration easy.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications KFD0-TR-1 038307

General specifications
Signal typeAnalog input
Supply
Rated voltage12 ... 35 V DC loop powered
Power dissipation0.4 W
Input
Connection sidefield side
Connectionterminals 1, 2-, 3+ suitable for Pt100, 2- and 3-wire connection
Lead resistancemax. 100 &Omega, per line
Measuring currentapprox. 1 mA
Output
Connection sidecontrol side
Connectionterminals 9+, 8-
Load(U -12 V) / 0.02 A
Current output4 ... 20 mA , limited to &le, 35 mA
Fault signalsensor burnout: upscaling &ge, 22 mA , limited to &le, 35 mA
Transfer characteristics
Measurement rangespan without linearization 25 ... 800 °C (77 ... 1472 °F)/ with linearisation 25 ... 375 °C (77 ... 707 °F) zero point without linearization -200 ... 400 °C (-328 ... 752 °F)/ with linearisation -30 ... 375 °C (-22 ... 707 °F) span and zero point adjustable
Deviation
After calibration0.1 % of full-scale value
Influence of ambient temperaturespan and zero point 0.015 % / K or ± 10 m&Omega, / K
Influence of supply voltage6.5 ppm/V
Rise time250 ms
Galvanic isolation
Input/Outputsafe isolation acc. to DIN VDE 0106, rated insulation voltage 253 Veff
Indicators/settings
Control elementsDIP-switch rotary switch
Configurationvia DIP switches via rotary switch
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Insulation coordinationEN 50178
Galvanic isolationEN 50178
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.