General specifications |
Switching function | Normally closed (NC) |
Output type | NAMUR |
Rated operating distance | 4 mm |
Installation | flush |
Assured operating distance | 0 ... 3.04 mm |
Reduction factor rAl | 0.15 |
Reduction factor rCu | 0.05 |
Reduction factor r304 | 0.55 |
Output type | 2-wire |
Nominal ratings |
Nominal voltage | 8 V |
Switching frequency | 0 ... 1000 Hz |
Hysteresis | &le, 20 % at 200°C |
Suitable for 2:1 technology | yes , Reverse polarity protection diode not required |
Current consumption | |
| Measuring plate not detected | min. 3 mA |
| Measuring plate detected | &le, 1 mA |
Compliance with standards and directives |
Standard conformity | |
| NAMUR | EN 60947-5-6:2000
IEC 60947-5-6:1999 |
| Standards | EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012 |
Approvals and certificates |
UL approval | |
| Ordinary Location | E87056 |
| Hazardous Location | E501628 |
| Control drawing | 116-0452 |
CCC approval | CCC approval / marking not required for products rated &le,36 V |
Ambient conditions |
Ambient temperature | 0 ... 200 °C (32 ... 392 °F) |
Mechanical specifications |
Connection type | cable SIHF , 10 m |
Core cross-section | 0.34 mm2 |
Housing material | Stainless steel 1.4305 / AISI 303 |
Sensing face | PPS |
Degree of protection | IP65 |
Cable | |
| Bending radius | > 10 x cable diameter |
Note | amplifier -25°C...70°C
2 m PTFE cable between amplifier and oscillator |
Data for application in connection with hazardous areas |
Equipment protection level | Ga , Gb , Da |
Equipment protection level Ga |
Type of protection | intrinsic safety |
CE marking | [*PD-Z02585A*] |
Certificates | |
| Appropriate type | NJ4-30GM-N-200... |
| ATEX certificate | PTB 00 ATEX 2048 X |
| ATEX marking | II 1G Ex ia IIC T6&hellip,T1 Ga |
| Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
Effective internal capacitance | max. 70 nF
A cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H
A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
Refer to the relevant certificate to see the relationship between the connected circuit type, the maximum permitted ambient temperature, the effective inner reactances, and if applicable the surface temperature or the temperature class. |
| for ATEX | at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW ,
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW ,
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW |
Equipment protection level Gb |
Type of protection | intrinsic safety |
CE marking | [*PD-Z02585A*] |
Certificates | |
| Appropriate type | NJ4-30GM-N-200... |
| ATEX certificate | PTB 00 ATEX 2048 X |
| ATEX marking | II 1G Ex ia IIC T6&hellip,T1 Ga |
| Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
Effective internal capacitance | max. 70 nF
A cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H
A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
Refer to the relevant certificate to see the relationship between the connected circuit type, the maximum permitted ambient temperature, the effective inner reactances, and if applicable the surface temperature or the temperature class.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW ,
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW ,
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW |
Equipment protection level Da |
Type of protection | intrinsic safety |
CE marking | [*PD-Z02585A*] |
Certificates | |
| Appropriate type | NJ4-30GM-N-200... |
| ATEX certificate | PTB 00 ATEX 2048 X |
| ATEX marking | II 1D Ex ia IIIC T135°C Da |
| Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
Effective internal capacitance | max. 70 nF
A cable length of 10 m is considered. |
Effective internal inductance | max. 100 µ,H
A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
Refer to the relevant certificate to see the relationship between the connected circuit type, the maximum permitted ambient temperature, the effective inner reactances, and if applicable the surface temperature or the temperature class.
at Ui = 16 V , Ii = 25 mA , Pi = 34 mW ,
at Ui = 16 V , Ii = 25 mA , Pi = 64 mW ,
at Ui = 16 V , Ii = 52 mA , Pi = 169 mW ,
at Ui = 16 V , Ii = 76 mA , Pi = 242 mW |
General information |
Use in the hazardous area | see instruction manuals |