Supply of spare parts for industrial enterprises around the world

Pepperl+Fuchs 316911

Current Driver  Pepperl+Fuchs 316911
Manufacturer
Pepperl+Fuchs
Part number
316911
Country
Germany
Type
Current Driver
Weight (g)
115
Sale of any product from the Pepperl+Fuchs catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Pepperl+Fuchs (official website: www.pepperl-fuchs.com). We sell only certified goods and give an official guarantee from the manufacturer Pepperl+Fuchs


This isolated barrier is used for intrinsic safety applications. The device repeats the input signal from a control system to drive SMART I/P converters, electrical valves, and positioners located in a hazardous area. Digital signals are superimposed on the analog values at the field side or control side and are transferred bi-directionally. The current is transferred via a DC/DC converter and repeated at the output terminals. An open field circuit presents a high impedance to the control side to allow alarm conditions to be monitored by the control system. Test sockets for the connection of HART communicators are integrated into the terminals of the device.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications 316911

General specifications
Signal typeAnalog output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionPower Rail or terminals 9+, 10-
Rated voltage19 ... 30 V DC
Ripple&le, 10 %
Rated current&le, 30 mA at 24 V
Power dissipation&le, 600 mW at 20 mA and 500 &Omega, load
Power consumption&le, 700 mW
Input
Connection sidecontrol side
Connectionterminals 5-, 6+
Input signal4 ... 20 mA , limited to approx. 26 mA
Input voltageopen loop voltage of the control system < 30 V
Voltage dropapprox. 6 V at 20 mA
Input resistance> 100 k&Omega,, with field wiring open
Output
Connection sidefield side
Connectionterminals 1+, 2-
Voltage&ge, 13 V at 20 mA
Current4 ... 20 mA
Load0 ... 650 &Omega,
Ripple20 mV rms
Transfer characteristics
Deviationat 20 °C (68 °F), 4 ... 20 mA < 0.1 % of full scale, incl. non-linearity and hysteresis
Influence of ambient temperature< 2 µ,A/K (-20 ... 70 °C (-4 ... 158 °F))
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Rise time10 to 90 % &le, 10 ms
Galvanic isolation
Input/Outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLED
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012 EN 61326-3-2:2008
Degree of protectionIEC 60529
Protection against electrical shockUL 61010-1:2012
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateCESI 06 ATEX 021
Marking II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
OutputEx ia
Supply
Maximum safe voltage250 V AC (Attention! Um is no rated voltage.)
Equipmentterminals 1+, 2-
Voltage Uo25.2 V
Current Io100 mA
Power Po630 mW
Internal capacitance Ci5.7 nF
Internal inductance Li negligible
CertificateCESI 19 ATEX 021 X
Marking II 3G Ex ec IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015
International approvals
FM approval
FM certificateFM 18 CA 0116 X , FM 19 US 0117 X
Control drawing116-0469 (cFMus)
UL approvalE106378
Control drawing116-0459 (cULus)
IECEx approval
IECEx certificateIECEx CES 06.0001X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)